35 Ill. Adm. Code 217.710

Monitoring

Last amended: 2001Year: 2026Length: 196 wordsOfficial source
Section 217 Section 217.710  Monitoring a)         The owner or operator of an EGU subject to this Subpart shall install, calibrate, maintain and operate continuous emissions monitoring systems (CEMS) for NO x that meet the requirements of 40 CFR 75, subpart B. b)         Notwithstanding subsection (a), the owner or operator of a gas-fired peaking unit or oil-fired peaking unit as defined in 40 CFR 72.2 may determine NO x emissions in accordance with the emissions estimation protocol of 40 CFR 75, subpart E. c)         Notwithstanding subsection (a), the owner or operator of a combustion turbine that operates less than 350 hour per ozone control period may determine the heat input and NO x emissions of the turbine as follows: 1)         Heat input shall be determined from the metered fuel usage to the turbine or the calculated heat input determined as the product of the turbine's maximum hourly heat input and hours of operation as recorded by operating instrumentation on the turbine; 2)         NO x emissions shall be determined as the product of the heat input, as determined above, and the appropriate default NO x emission factors below: 0.7 lbs/mmbtu – Natural gas 1.2 lbs/mmbtu – Fuel oil