35 Ill. Adm. Code 218.124
External Floating Roofs
Section 218
Section 218.124 External
Floating Roofs
a) In addition to meeting the requirements of Section 218.123(b)
of this Part, no owner or operator of a stationary storage tank equipped with
an external floating roof shall cause or allow the storage of any volatile
petroleum liquid in the tank unless:
1) The tank has been fitted:
A) With a continuous secondary seal extending from the floating
roof to the tank wall (rim mounted secondary seal), or
B) With any other equipment or means of equal efficiency approved
by the Agency according to the provisions of 35 Ill. Adm. Code 201, and further
processed consistent with Section 218.108 of this Part;
2) Each seal closure device meets the following requirements:
A) The seal is intact and uniformly in place around the
circumference of the floating roof between the floating roof and tank wall; and
B) The accumulated area of gaps exceeding 0.32 centimeter (⅛
inch) in width between the secondary seal and the tank wall shall not exceed
21.2 square centimeters per meter of tank diameter (1.0 square inches per foot
of tank diameter). Compliance with this requirement shall be determined by:
i) Physically measuring the length and width of all gaps around
the entire circumference of the secondary seal in each place where a 0.32 cm
(0.125 in.) uniform diameter probe passes freely (without forcing or binding
against the seal) between the seal and the tank wall; and
ii) Summing the area of the individual gaps.
3) Emergency roof drains are provided with slotted membrane
fabric covers or equivalent covers across at least 90 percent of the area of
the opening;
4) Openings are equipped with projections into the tank which
remain below the liquid surface at all times;
5) Inspections are conducted prior to May 1 of each year to
insure compliance with subsection (a) of this Section;
6) The secondary seal gap is measured prior to May 1 of each year
and within 30 days of a written request to demonstrate compliance with
subsection (2)(B) of this Section;
7) Records of the types of volatile petroleum liquid stored, the
maximum true vapor pressure of the liquid as stored, the results of the
inspections and the results of the secondary seal gap measurements are
maintained and available to the Agency, upon verbal or written request, at any
reasonable time for a minimum of two years after the date on which the record
was made.
b) Subsection (a) above does not apply to any stationary storage
tank equipped with an external floating roof:
1) Exempted under Section 218.123(a)(2) through 218.123(a)(6) of
this Part;
2) Of welded construction equipped with a metallic type shoe seal
having a secondary seal from the top of the shoe seal to the tank wall
(shoe-mounted secondary seal);
3) Of welded construction equipped with a metallic type shoe
seal, a liquid-mounted foam seal, a liquid-mounted liquid-filled-type seal, or
other closure device of equivalent control efficiency approved by the Agency in
which a petroleum liquid with a true vapor pressure less than 27.6 kPa (4.0
psia) at 294.3° K (70° F) is stored; or
4) Used to store crude oil with a pour point of 50° F or higher
as determined by ASTM Standard D97-66 incorporated by reference in Section
218.112 of this Part.