35 Ill. Adm. Code 218.582
Bulk Gasoline Terminals
Section 218
Section 218.582Â Bulk
Gasoline Terminals
a)Â Â Â Â Â Â Â Â No person shall cause or allow the transfer of gasoline into
any delivery vessel from any bulk gasoline terminal unless:
1)Â Â Â Â Â Â Â Â The bulk gasoline terminal is equipped with a vapor control
system that limits emission of VOM to 80 mg/l (0.00067 lbs/gal) of gasoline
loaded;
2)Â Â Â Â Â Â Â Â The vapor control system is operating and all vapors displaced
in the loading of gasoline to the delivery vessel are vented only to the vapor
control system;
3)Â Â Â Â Â Â Â Â There is no liquid drainage from the loading device when it is
not in use;
4)Â Â Â Â Â Â Â Â All loading and vapor return lines are equipped with fittings
which are vapor tight; and
5)Â Â Â Â Â Â Â Â The delivery vessel displays the appropriate sticker pursuant
to the requirements of Section 218.584(b) or (d) of this Part; or, if the
terminal is driver-loaded, the terminal owner or operator shall be deemed to be
in compliance with this Section when terminal access authorization is limited
to those owners and/or operators of delivery vessels who have provided a
current certification as required by Section 218.584(c)(3) of this Part.
b)Â Â Â Â Â Â Â Â The operator of a bulk gasoline terminal shall:
1)Â Â Â Â Â Â Â Â Operate the terminal vapor collection system and gasoline
loading equipment in a manner that prevents:
A)Â Â Â Â Â Â Â Gauge pressure from exceeding 18 inches of water and vacuum from
exceeding 6 inches of water as measured as close as possible to the vapor hose
connection; and
B)Â Â Â Â Â Â Â A reading equal to or greater than 100 percent of the lower
explosive limit (LEL measured as propane) when tested in accordance with the
procedure described in EPA 450/2-78-051 Appendix B, incorporated by reference
in Section 218.112 of this Part; and
C)Â Â Â Â Â Â Â Avoidable leaks of liquid during loading or unloading
operations.
2)Â Â Â Â Â Â Â Â Provide a pressure tap or equivalent on the terminal vapor
collection system in order to allow the determination of compliance with
Section 218.582(d)(1)(A) of this Part; and
3)Â Â Â Â Â Â Â Â Within 15 business days after discovery of the leak by the
owner, operator, or the Agency repair and retest a vapor collection system
which exceeds the limits of subsection (c)(1)(A) or (B) of this Section.