35 Ill. Adm. Code 219.582
Bulk Gasoline Terminals
Section 219
Section 219.582 Bulk
Gasoline Terminals
a) No person shall cause or allow the transfer of gasoline into
any delivery vessel from any bulk gasoline terminal unless:
1) The bulk gasoline terminal is equipped with a vapor control
system that limits emission of VOM to 80 mg/1 (0.00067 lbs/gal) of gasoline
loaded;
2) The vapor control system is operating and all vapors displaced
in the loading of gasoline to the delivery vessel are vented only to the vapor
control system;
3) There is no liquid drainage from the loading device when it is
not in use;
4) All loading and vapor return lines are equipped with fittings
which are vapor tight; and
5) The delivery vessel displays the appropriate sticker pursuant
to the requirements of Section 219.584(b) or (d) of this Part; or, if the
terminal is driver-loaded, the terminal owner or operator shall be deemed to be
in compliance with this Section when terminal access authorization is limited
to those owners and/or operators of delivery vessels who have provided a
current certification as required by Section 219.584(c)(3) of this Part.
b) The operator of a bulk gasoline terminal shall:
1) Operate the terminal vapor collection system and gasoline
loading equipment in a manner that prevents:
A) Gauge pressure from exceeding 18 inches of water and vacuum from
exceeding 6 inches of water as measured as close as possible to the vapor hose
connection; and
B) A reading equal to or greater than 100 percent of the lower
explosive limit (LEL measured as propane) when tested in accordance with the
procedure described in EPA 450/2-78-051 Appendix B, incorporated by reference
in Section 219.112 of this Part; and
C) Avoidable leaks of liquid during loading or unloading
operations.
2) Provide a pressure tap or equivalent on the terminal vapor
collection system in order to allow the determination of compliance with
Section 219.582(d)(1)(A) of this Part; and
3) Within 15 business days after discovery of the leak by the
owner, operator, or the Agency repair and retest a vapor collection system
which exceeds the limits of subsection (c)(1)(A) or (B) of this Section.