35 Ill. Adm. Code 229.162
Inspection Requirements for All HMIWIs
Section 229
Section 229.162 Inspection
Requirements for
All HMIWIs
a) Before January 1, 2014, each owner or operator of a rural
HMIWI subject to the emission limits under Section 229.126 of this Part shall
inspect the HMIWI according to the following schedule:
1) An initial inspection shall be conducted by September 15,
2000; and
2) An annual inspection shall be conducted by September 15 of
each year thereafter.
b) Each equipment inspection shall be conducted to ensure the
proper operation of the HMIWI and, at a minimum, shall consist of the following
steps:
1) An inspection of all burners, pilot assemblies, and pilot
sensing devices, cleaning the pilot flame sensor, as necessary;
2) An inspection of the primary and secondary chamber combustion
air flow, adjusting, as necessary;
3) An inspection of the hinges and door latches, lubricating, as
necessary;
4) An inspection of dampers, fans, and blowers;
5) An inspection of the HMIWI door and door gaskets;
6) An inspection of all HMIWI motors;
7) An inspection of the primary chamber refractory lining,
cleaning, repairing or replacing the lining, as necessary;
8) An inspection of the incinerator shell for corrosion or hot
spots;
9) An inspection of the secondary/tertiary chamber and stack,
cleaning as necessary;
10) Where applicable, an inspection of the mechanical loader,
including limit switches;
11) A visual inspection of the waste bed (grates), repairing or
sealing, as necessary;
12) Where applicable, an inspection of air pollution control
devices to ensure their proper operation;
13) Where applicable, an inspection of the waste heat boiler
systems;
14) An inspection of all bypass stack components;
15) Calibration of thermocouples, sorbent feed systems and
monitoring equipment; and
16) A general inspection of all equipment to ensure that it is
maintained in good operating condition.
c) The owner or operator of an HMIWI shall document that, during
the burn cycle immediately following the inspection required by this Section,
the HMIWI is operating properly and make any necessary adjustments.
d) All maintenance, adjustments, or repairs identified during the
equipment inspection required under this Section shall be completed within 10
days after the inspection. The owner or operator of an HMIWI may have a longer
period of time in which to complete any repairs identified as a result of the
inspection required by this Section, provided that it makes this request to the
Agency in writing, and the Agency approves the owner or operator of an HMIWI's
request in writing.
e) The
owner or operator of a small, rural, medium, or large HMIWI subject to the emission
limits under Section 229.125(c) as applicable, or Section 229.126 of this Part,
shall inspect the HMIWI as outlined in subsection (b) of this Section,
according to the following schedule:
1) An
initial equipment inspection shall be conducted by January 1, 2014; and
2) An
annual equipment inspection shall be conducted by January 1 of each year
thereafter.
f) The
owner or operator of an HMIWI subject to the emissions limits under Section
229.125(c) as applicable, or Section 229.126(c) of this Part, shall inspect the
air pollution control devices, according to the following schedule:
1) An
initial air pollution control device inspection shall be conducted by January
1, 2014; and
2) An
annual air pollution control device inspection shall be conducted by January 1
of each year thereafter.
g) Each
air pollution control device inspection, as applicable, shall be conducted to
ensure the proper operation of the device and, at a minimum, shall consist of
the following steps:
1) Where
applicable, an inspection of the thermocouples, sorbent feed systems, and any
other monitoring equipment, adjusting applicable calibrations, as necessary;
and
2) A
general inspection of the equipment to ensure that it is maintained in good
operating condition.
h) All
maintenance, adjustments, or repairs identified during an air pollution control
device inspection required under this Section shall be completed within 10 days
after the inspection. The owner or operator of an HMIWI may have a longer
period of time in which to complete any repairs identified as a result of the
inspection required by this Section, provided that it makes this request to the
Agency in writing and the Agency approves the request in writing.