35 Ill. Adm. Code 307.1103
Cyanide
Section 307
Section 307.1103Â Cyanide
a)Â Â Â Â Â Â Â Â Waste to any public sewer system must not contain more than 10
mg/L total cyanide, and any sample tested must not release more than 2 mg/L of
cyanide when tested at a pH of 4.5 and a temperature of 66 ºC (150 ºF) for 30
minutes, except as permitted by subsection (b).
b)Â Â Â Â Â Â Â Â Upon application by a county, municipality, sanitary district,
or public utility and approval by the Agency, based upon the Agency's
determination that no violation of the effluent standards of 35 Ill. Adm. Code
304 or hazard to workers in that sewage works will result, limited additional
amounts of cyanide exceeding the standards in subsection (a) may be discharged
to the sewage works of that county, sanitary district, municipality, or public
utility.
c)Â Â Â Â Â Â Â Â Nothing in this Section may be construed as limiting the
authority of any county, municipality, sanitary district, or public utility to
impose any more stringent standards or limitations on cyanide discharges to its
sewage works.
d)Â Â Â Â Â Â Â Â Any actions undertaken under subsection (b) will be subject to
the limitations of Section 307.2400(b)(7).