35 Ill. Adm. Code 370.1120
High Rate Filtration
Section 370
Section 370.1120 High Rate
Filtration
a) Design Considerations
Care should be given in the selection of pumping equipment
ahead of filter units to minimize shearing of flow particles. Consideration
should be given in the plant design to providing flow-equalization facilities
to moderate filter influent quality and quantity.
b) Pretreatment
A positive method shall be provided to control the suspended
solids loading to the filters. Equipment for the feeding of chemical coagulant
aids prior to secondary settling shall be provided unless other equally
effective means of suspended solids control are used.
c) Multiple Units
Multiple units shall be provided. At least three units
should be provided. Units shall be capable of independent operation and
maintenance.
d) Filtration Rates
The peak hourly flow rate applied to the filter shall not
exceed 5 gpm/sq. ft. of filter area, computed with one unit out of service.
1) Rate Controls
Controls shall be provided which allow adjustment and control
of the rate of flow to each filter unit.
2) Flow Measurement
The flow to each filter shall be monitored by indicating
equipment.
e) Accessibility and Maintenance
Each filter unit shall be designed and installed so that
there is ready and convenient access to all components and the media surface
for inspection and maintenance without taking other units out of service.
f) Housing
Housing of filter units shall be provided. The housing shall
be constructed of suitable corrosion-resistant materials. All controls shall
be enclosed, and the structure housing the filter, controls and equipment shall
be provided with heating and ventilation adequate to minimize problems with
excess humidity.
g) Construction Details
1) Underdrains
The underdrain system shall be designed for uniform
distribution of flow of backwash water (and air, if provided) without danger of
clogging from solids in the backwash water. A positive means of pressure
relief shall be provided for the underdrain system to prevent structural damage
by excessive backwash pressures. The selection of the underdrain system shall
be based on demonstrated satisfactory field experience under similar
conditions.
2) Media
The selection of proper media sizes and types depends upon
the filtration rate selected, the type of treatment provided the influent to
the filter, filter configuration, and effluent quality objectives. In dual or
multi-media filters, media size and type selection must consider compatibility
among media. Media shall be selected and provided to meet specific conditions
and treatment requirements relative to the project under consideration. The
selection and sizing of the media shall be based on demonstrated satisfactory
field experience under similar conditions. All media shall have a uniformity
coefficient of 1.7 or less. The uniformity coefficient, effective size, depth
and type of media shall be set forth in the specification.
3) Appurtenances
The design of the filter appurtenances shall be based on
demonstrated satisfactory field experience under similar conditions. The
filters shall be equipped with the following:
A) Wash water troughs.
B) Surface wash, air scouring equipment or mechanical agitation
designed to adequately remove entrapped solids from the media.
C) Equipment for measuring filter head loss.
D) Filter influent and effluent sampling points.
Also refer to subsections (h)(2), (h)(4) and (i) below.
h) Backwash
1) Rate and Duration
The backwash rate shall be adequate to fluidize and expand
each media layer a minimum of 20 percent based on the media selected. Minimum
and maximum backwash rates shall be based on demonstrated satisfactory field
experience under similar conditions. The design shall provide for a minimum
backwash period of 10 minutes. Excessive backwash rates may cause washout of
the filter media.
2) Control and Flow Measurement
A positive means of shutting off flow to a filter shall be
provided. Controls shall be provided which permit adjustment of both the
backwash rate and the backwash period. Flow measurement of the backwash flow
rate shall be provided. A staff gauge or wall mounted scale to allow use of
the rise rate for flow measurement may be used.
3) Clearwell
A clearwell or other plant tankage isolated from unfiltered
flows shall be provided as a source of backwash water. Filtered plant effluent
shall be used as backwash water. The volume of storage provided shall be
sufficient to allow sequential backwashing of at least 2 filter units at the
design backwash rate.
4) Chlorination of Filter Backwash
Provision shall be made for periodic chlorination of filter
backwash water (or filter influent) to control slime growths. The flows from
the cleaning of the filters shall be returned to the head of the plant. Refer
to subsection (h)(6)(A) below.
5) Backwash Pumps
Where used, backwash pumps shall be provided in multiple
units, designed for independent operation and maintenance. Pumps shall be sized
in accordance with subsection (h)(1) above to provide the required backwash
rate with one unit out of service and should be of equal size. The total
dynamic head of the pump shall be limited to that needed for the application so
that undue stress of the underdrain system will not occur. Refer to subsection
(g)(1) above.
6) Mudwell
A mudwell or other plant tankage shall be provided to hold
backwash water from the filters. The volume provided shall be sufficient to
hold the water generated by the backwashing of two filter units including the
water in and above the filter media prior to filtration. Refer to subsection
(h)(1) above. Filter backwash shall be returned to process or otherwise
treated to insure compliance with applicable standards.
A) Return Rate
The rate of return of filter backwash to the treatment units
shall not exceed 15 percent of the design average flow to the treatment units.
Refer to subsection (j)(1) below and Section 370.520(g).
B) Mudwell Return Pumps
Backwash return pumps, where used, shall be provided in
multiple units designed for independent operation and maintenance. The units
shall be sized to provide the required pumping rate with the largest unit out
of service. Refer to subsection (h)(6)(A) above.
i) Control Panel
Automatic controls shall be provided, with a manual override
on the control panel for operating equipment, including each individual valve
essential to the filter operation.
j) Miscellaneous Considerations
1) Return Backwash Loadings
The return of backwash water and solids will result in
increases in the hydraulic and suspended solids loads to the preceding
treatment units. Design of these units shall take into account the increased
loads.
2) Oil and Grease
Filters at treatment plants treating wastewaters containing
above normal concentrations of greases or similar materials should be of the
gravity type. Facilities should be considered for the periodic addition of
chemicals to remove greases in such cases.
3) Proprietary Equipment
Proprietary equipment not conforming to the requirements of
this section will be evaluated on a case-by-case basis in accordance with
Section 370.520(b).