35 Ill. Adm. Code 370.700
General Considerations
Section 370
Section 370.700 General
Considerations
a) Number of Units
Multiple units capable of independent operation are desirable
and shall be provided in all plants where design average flows exceed 100,000
gallons per day. Plants not having multiple units shall include other
provisions to assure continuity of treatment.
b) Arrangement
Settling tanks shall be arranged in accordance with Sections
370.520(e) and 370.710(g).
c) Flow Distribution
Effective flow splitting devices and control appurtenances
shall be provided to insure proper organic and hydraulic proportion of flow to
each unit. Refer to Section 370.520(f).
d) Tank Configuration
Consideration should be given to the probable flow pattern in
the selection of tank size and shape, and inlet and outlet type and location.