35 Ill. Adm. Code 370.900
Trickling Filters
Section 370
Section 370.900 Trickling
Filters
a) General
1) Applicability
Trickling filters may be used for treatment of sewage
amenable to treatment by aerobic biologic processes. Trickling filters shall be
preceded by settling tanks equipped with scum and grease collecting devices, or
other suitable pretreatment facilities.
2) Design Basis
Filters shall be designed so as to provide the required
reduction in biochemical oxygen demand, ammonia nitrogen, or to properly
condition the sewage for subsequent treatment processes.
3) Multiple Units
Multiple trickling filter units capable of independent
operation are recommended for all plants and must be provided for those plants
where the design average flow exceeds 100,000 gallons per day. Plants not
having multiple units shall include other provisions to assure continuity of treatment.
b) Dosing Equipment
1) Distribution
A) All hydraulic factors involving proper distribution of sewage
on the filter should be carefully calculated and submitted with the basis of
design.
B) The sewage may be distributed over the filter by rotary
distributors or other suitable devices which will permit reasonably uniform
distribution to the surface area. At design average flow, the deviation from
calculated uniformly distributed volume per square foot of the filter surface
shall not exceed plus or minus 10 percent at any point.
2) Dosing and Recirculation
A) Sewage may be applied to the filters by siphons, pumps or by
gravity discharge from preceding treatment units when suitable flow
characteristics have been developed. Application of the sewage should be
continuous except for low rate filters. A hydraulic system for recirculation
shall be provided for new facilities and should be considered where existing
trickling filter units are included in treatment plant upgrading.
B) The piping system, including dosing equipment and distributor,
shall be designed to provide capacity for the peak hourly flow rate including
recirculation rates determined under subsection (h).
3) Distributor Head Requirements
For reaction type distributors, a minimum head of 24 inches
between low water level in siphon chamber and center of arms is required.
Similar allowances shall be made in design for added pumping head requirements
where pumping to the reaction type distributor is used. The design shall
include the head required at the center column for the full range of flows, taking
into account all head losses from the center column back to the dosing facility
at all water levels. Calculations shall be submitted to justify the basis of
design.
4) Clearance
A minimum clearance of 6 inches between media and distributor
arms shall be provided. Refer to subsection (e)(4).
c) Media
1) Quality
The media may be crushed rock, slag or specially manufactured
material. The media shall be durable, resistant to spalling or flaking, and be
relatively insoluble in sewage. The top 18 inches shall have a loss by the
20-cycle, sodium sulfate soundness test of not more than 10 percent, as
prescribed by ASCE Manual of Engineering Practice, Number 13, the balance to
pass a 10-cycle test using the same criteria. Slag media shall be free from
iron. Manufactured media shall be resistant to ultraviolet degradation,
disintegration, erosion, aging, all common acid and alkalies, organic
compounds, and fungus and other biological attack. Such media shall be
structurally capable of supporting a man's weight or a suitable access walkway
shall be provided to allow for distributor maintenance.
2) Depth
The filter media shall have a minimum depth of 6 feet above
the underdrains. For rock media filters (subsection (c)(3)(A)), only the top 7
feet of the volume of the filter shall be considered in BOD removal credit
computations. For manufactured media filters see subsection (c)(3)(B).
3) Size and Grading of Media
A) Rock, Slag and Similar Media
i) Rock, slag and similar media shall not contain more than 5
percent by weight of pieces whose longest dimension is 3 times the least
dimension.
ii) Media shall be free from thin elongated and flat pieces,
dust, clay, sand, or fine material and shall conform to the following size and
grading when mechanically graded over vibrating screen with square openings:
Passing 4 1/2 inch screen – 100% by weight
Retained on 3 inch screen – 95-100% by weight
Passing 2 inch screen – 0-2% by weight
Passing 1 inch screen – 0-1% by weight
B) Manufactured Media
Suitability of size, space, media configuration and depth
will be evaluated on the basis of experience with installations handling
similar wastes and loadings. To ensure sufficient void clearance, media with a
specific surface area of no more than 30 square feet per cubic foot may be used
for filters employed for carbonaceous reduction, and media with a specific
surface area of no more than 45 square feet per cubic foot may be used for
second stage ammonia reduction. See subsection (c)(1) for quality
requirements.
4) Handling and Placing of Media
A) Material delivered to the filter site shall be stored on wood
planks or other approved clean hard surfaced areas.
B) All material shall be rehandled at the filter site and no
material shall be dumped directly into the filter. Crushed rock, slag and
similar media shall be rescreened or forked at the filter site to remove all
fines.
C) The material shall be placed by hand to a depth of 12 inches
above the tile underdrains and all material shall be carefully placed so as not
to damage the underdrains. The remainder of the material may be placed by
means of belt conveyors or equally effective methods approved by the engineer.
D) Manufactured media shall be handled and placed as recommended
by the manufacturer and approved by the engineer.
E) Trucks, tractors, or other heavy equipment shall not be driven
over the filter during or after construction.
d) Underdrainage System
1) Arrangement
Underdrains with semi-circular inverts or equivalent should
be provided and the underdrainage system shall cover the entire floor of the
filter. Inlet openings into the underdrains shall have an unsubmerged gross
combined area equal to at least 15 percent of the surface area of the filter.
2) Slope
The underdrains shall have a minimum slope of 1 percent.
Effluent channels shall be designed to produce a minimum velocity of 2 feet per
second at design average flow of application to the filter and shall have
adequate capacity for the peak hourly flow rate including the required
recirculation flows.
3) Flushing
Provision should be made for flushing the underdrains. In
small filters, use of a peripheral head channel with vertical vents is
acceptable for flushing purposes. Inspection facilities should be provided.
4) Ventilation Requirements for Underdrains
The underdrainage system, effluent channels, and effluent
pipe should be designed to permit free passage of air. The size of drains,
channels, and pipe should be such that not more than 50 percent of their
cross-sectional area will be submerged under the design hydraulic loading.
Consideration should be given in the design of the effluent channels to the
possibility of increased hydraulic loading.
e) Special Features
1) Flooding
Provision shall be made in the design of conventional rock
filter structures so that the media may be flooded.
2) Maintenance
All distribution devices, underdrains, channels and pipes
shall be designed so that they may be properly maintained, flushed or drained.
3) Flow Measurement
Devices shall be provided to permit measurement of flow to
the filter, and of recirculated flows.
4) Protection From Freezing
Trickling filters shall be covered to protect from freezing,
and to maintain operation and treatment efficiencies. The filter cover shall
be constructed of appropriate corrosion resistant materials and designed to
allow operator access for maintenance, repair and replacement of the filter
dosing equipment.
5) Ventilation of Covered Filters
Forced ventilation shall be provided for covered trickling
filters to insure adequate oxygen for process requirements. Windows or simple
louvered mechanisms so arranged to insure air distribution throughout the
enclosure shall be provided. The ventilation facilities shall be designed to
allow operator control of air flow in accordance with outside temperature.
Design computations showing the adequacy of air flow to satisfy process oxygen
requirements shall be submitted.
f) Two-Stage Filters
The foregoing standards also apply to second stage filters.
g) Special Applications
1) Roughing Filters
In some instances it is desirable to partially reduce the
organic strength of wastewaters. In such cases trickling filters may be used
for roughing treatment. Design parameters and contaminant removal efficiencies
will be approved on a case-by-case basis. Refer to subsections (h)(2) and
(h)(3).
2) Nitrifying Filters
Trickling filters may, under favorable conditions, be used as
nitrification devices. Design parameters and contaminant removal efficiencies
will be approved on a case-by-case basis. Refer to Section 370.1210(d).
h) Efficiency
1) Single Stage, Settling Tank – No Recirculation
Expected reduction of BOD of settled normal domestic
wastewater by a single stage filter, packed with crushed rock, slag or similar
material and with subsequent settling, shall be determined from Appendix F,
Figure No. 3. In developing this curve, loading due to recirculated sewage has
not been considered.
2) Single or Multi-Stage, Settling Tank – Recirculation
Expected BOD removal efficiencies may also be determined by
theoretical and empirical formula if accompanied by detailed explanation,
particularly for roughing filters and for filters with recirculation. (Refer
to WEF Manual of Practice (MOP) No. 8, "Design of Municipal Wastewater
Treatment Plants", vol. 1 (1992).)
3) Single or Multi-Stage, No Settling Tank – Recirculation
Filters not followed by a settling tank and discharging into a subsequent
treatment process shall not be credited with BOD removal efficiencies as in
subsections (h)(1) and (h)(2) above. Expected performance in such cases, including
filters packed with manufactured media, shall be determined from prototype
testing and full-scale plant experience.