35 Ill. Adm. Code 370.940
Intermittent Sand Filtration for Secondary Treatment
Section 370
Section 370.940 Intermittent
Sand Filtration for Secondary Treatment
a) Applicability
Use of the intermittent sand filter for secondary treatment
is generally limited to weak to normal strength wastewaters which are amenable
to biological treatment. Cold weather operational problems may preclude the use
of this process unless the influent temperature to the filter is adequate to
allow efficient filter operation necessary to meet the applicable effluent
standards.
b) Pretreatment Requirements
Wastewaters applied to intermittent sand filters must be
substantially free of grit, debris, oil and grease, floating and suspended
materials, and components which inhibit biological processes and cause rapid
clogging of the filter. Special consideration shall be given to the design of
preceding treatment units, including dosing facilities, to limit heat loss
during winter operation.
c) Multiple Units
Intermittent sand filters shall be provided in multiple
units, designed for independent operation and maintenance.
d) Location
Intermittent sand filters treating septic tank or primary
effluent should be restricted to relatively isolated locations or otherwise
modified in order to minimize odor nuisances.
e) Recirculation
Recirculation of filter effluent may be practiced in order to
attenuate and equalize organic and hydraulic loads to the filter, and improve
unit process efficiency, control odors, and improve day-to-day reliability.
1) Rate
A recirculation rate of up to 300% of the settled sewage load
to the filter may be provided.
2) Variability
The capability of varying the recirculation rate allows
greater process control and optimization of process efficiency. This feature
shall be included where recirculation is provided.
f) Dosing
1) Dosing Volumes
The dosing facilities shall be designed for a capacity of
2,500 gallons per 1,000 sq. ft. of filter bed to be dosed at any given time.
2) Dosing Rates for Siphons or Pumps
Siphons (at minimum head) or pumps shall have a discharge
capacity at least 100% in excess of the maximum rate of inflow to the dosing
tank, including recirculation, and at average head, at least 90 gallons per
minute per 1,000 square feet.
3) Discharge Line Capacity
The discharge lines to the beds shall have sufficient
capacity to permit the full rated discharge of the siphons or pumps.
g) Construction Details
1) Earth Base
The earth base of the filters shall be sloped to the
underdrains.
2) Underdrains
The sand filter shall be provided with open-joint or
perforated pipe underdrains. They should be sloped to the outlet and spaced
not to exceed 10 foot centers. Vertical riser vents shall be provided at both
ends of each underdrain pipe and shall be located as not to be overtopped at
maximum dosing depth.
3) Media
A) Gravel Base
Clean graded gravel, preferably placed in at least three
layers, should be placed around the underdrains and to a depth of at least 6
inches over the top of the underdrains. Crushed stone may not be used in lieu
of gravel. Suggested gradings for the three layers are:
1½" to ¾", ¾" to ¼", ¼" to ⅛".
B) Sand
At least 24 inches of clean washed sand shall be provided.
Sand shall be durable and relatively insoluble in sewage. Clay content shall
be less than 1% by weight. The effective size shall be 0.3 to 1.0 millimeter
(mm). The uniformity coefficient shall not be greater than 3.5.
4) Splash Slabs
Splash slabs shall be provided at each point of discharge to
the filter. A means of dissipating the energy of the discharge velocity shall
be provided around the periphery of the splash slab.
5) Curbs
Provision shall be made to prevent soil and surface runoff
from entering the filter area. Curbs should be high enough to hold the maximum
dose and provide adequate freeboard.
6) Distribution System
A) Arrangement
Provision shall be made for even distribution of the flow on
the filter surface. If troughs or piping are used, they shall be so located
that the maximum lateral travel of the flow on the media surface is not more
than 20 feet.
B) Drains
Troughs, discharge piping or other distribution equipment
shall be sloped to drain to prevent freezing.
h) Loading Rates
The loading rates shall be based on the raw sewage flow and
organic strength. The following loading rates shall not be exceeded:
Raw Waste Strength
(Bod
5
mg/l)
Dose
Rate
(gals./ft.
2
/day
100 to 200
3
200 to 300
2
above 300
1