35 Ill. Adm. Code 370.APPENDIX C

C Table No. 3 – Air Test Table for Sanitary Sewer Leakage Testing*

Last amended: 1997Year: 2026Length: 214 wordsOfficial source
Section 370.APPENDIX C   Table No. 3 – Air Test Table for Sanitary Sewer Leakage Testing* SPECIFICATION TIME (MIN:SEC) REQUIRED FOR PRESSURE DROP FROM 3½ TO 2½ PSIG WHEN TESTING ONE PIPE DIAMETER ONLY Length of Sewer Pipe In Feet PIPE DIAMETER, INCHES 4 6 8 10 12 15 18 21 24 25 0:04 0:10 0:28 0:28 0:40 1:02 1:29 2:01 2:38 50 0:09 0:20 0:35 0:55 1:19 2:04 2:58 4:03 5:17 75 0:13 0:30 0:53 1:23 1:59 3:06 4:27 6:04 7:55 100 0:18 0:40 1:10 1:50 2:38 4:08 5:56 8:05 10:34 125 0:22 0:50 1:28 2:18 3:18 5:09 7:26 9:55 11:20 150 0:26 0:59 1:46 2:45 3:58 6:11 8:30 175 0:31 1:09 2:03 3:13 4:37 7:05 200 0:35 1:19 2:21 3:40 5:17 12:06 225 0:40 1:29 2:38 4:08 5:40 10:25 13:36 250 0:44 1:39 2:56 4:35 8:31 11:35 15:07 275 0:48 1:49 3:14 4:43 9:21 12:44 16:38 300 0:53 1:59 3:31 10:12 13:53 18:09 350 1:02 2:19 3:47 8:16 11:54 16:12 21.10 400 1:10 2:38 6:03 9:27 13:36 18:31 24:12 450 1:19 2:50 6:48 10:38 15:19 20:50 27:13 500 1:28 5:14 7:34 11:49 17:01 23:09 30:14 *From Standard Specifications for Water and Sewer Main Construction in Illinois, Fourth Edition, May, 1986.  (Copies may be obtained from Illinois Society of Professional Engineers, Springfield, Illinois 62704.)