35 Ill. Adm. Code 372.300
Equipment Design
Section 372
Section 372.300 Equipment
Design
a) General Requirements
1) The design of all application systems shall provide facilities
to assure uniform distribution of the treated wastewater over the disposal
area.
2) Sufficient spare equipment and parts shall be available to
assure continuity of application during application periods.
3) A single irrigation pumping unit may be utilized if a spare
pump in working condition is available in dry storage.
4) The design shall provide for draining all pipes and equipment
to prevent freeze damage.
b) Non-Spray Surface Application Systems
Non-spray surface application systems which provide for even
distribution of wastewater effluent on the land site may be utilized, including
ridge and furrow, gated pipe, or equivalent systems. These systems may be
mobile or fixed on the site. They shall be designed to minimize clogging and
to allow for ease of maintenance.
c) Spray Irrigation Systems
1) Spray Equipment
A) Fixed head systems and center pivot rigs may be utilized. A
permanent connection point must be provided for each setting of moveable spray
irrigation equipment. The design shall include provisions for shutting off the
peripheral spray heads to prevent drift of spray beyond the application area
under design wind conditions.
B) The irrigation system controls shall be simple and be protected
from lightning damage.
C) The design maximum wind velocities shall be 15 MPH in urban and
residential areas and 25 MPH in agricultural areas.
2) Nozzle Pressure Regulation
Regulation of nozzle pressure to compensate for field
elevations and line losses shall be provided.