35 Ill. Adm. Code 372.500
Groundwater Monitoring
Section 372
Section 372.500 Groundwater
Monitoring
a) General
1) Saturated zone groundwater monitoring shall be provided for
all land application systems. A minimum of three groundwater monitoring wells
must be provided, one upgradient for determining background concentrations and
two downgradient in the dominant direction of groundwater movement from the
land application system.
2) Provision shall be made for sampling of the discharge from any
drainage tiles underlying the application area.
b) Potable Water Supply Wells
Where the project site is within 1,000 feet of existing
potable water wells but the wells are outside the minimum setback zone of the
Illinois Groundwater Protection Act [415 ILCS 55], groundwater monitoring wells
must be provided between each potable water well and the land application
system.
c) Monitoring Well Design
The monitoring wells shall be constructed with provisions for
sampling at the surface of the water table and at 5 feet below the water table
at each monitoring site.
d) Testing and Monitoring Equipment
Provision shall be made for testing groundwater for nitrates,
ammonia nitrogen, chlorides, sulfates, pH, total dissolved solids, phosphate,
and coliform bacteria as specified by the Agency permit for the project to
measure compliance with groundwater standards. Testing shall be performed in
accordance with 40 CFR 136 (1992) (no later amendments or editions), and may be
done either at an onsite laboratory or through a contractual arrangement with
an offsite laboratory.