35 Ill. Adm. Code 392.203
Criteria for Placing Sewers and Lift Stations on Restricted Status
Section 392
Section 392.203 Criteria for
Placing Sewers and Lift Stations on Restricted Status
a) The Agency may place sanitary sewers and lift stations on
Restricted Status in order to prevent overflows as expressly prohibited 35 Ill.
Adm. Code 306.103(b). Restricted Status may be imposed upon the confirmation
of overflows in the form of basement backups, overflows of sanitary sewer
manholes, or sanitary sewer overflow devices.
b) All combined and sanitary sewers and lift stations are subject
to Restricted Status when they become hydraulically overloaded, meaning unable
to accommodate the following flows:
1) Combined sewers and lift stations serving combined sewers must
be able to handle 350 percent of the average daily flow (based on best
available information) before overflowing.
2) Interceptors serving both combined sewers and sanitary sewers must
be able to accommodate 250 percent of the average daily dry weather flow (based
on best available information) from the sanitary sewers tributary thereto and
350 percent of the average daily dry weather flow from the combined sewers
tributary thereto before overflowing.