35 Ill. Adm. Code 6040.604.1010
Iron and Manganese Control
TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE F: PUBLIC WATER SUPPLIES
CHAPTER I: POLLUTION CONTROL BOARD
PART 604 DESIGN, OPERATION, AND MAINTENANCE CRITERIA
SECTION 604.1010 IRON AND MANGANESE CONTROL
Section 604.1010 Iron and Manganese Control
a) Except
as provided in 35 Ill. Adm. Code 611.300(e), treatment is required to meet the
iron and manganese MCL as stated in Section 611.300(b).
b) Removal of Iron and
Manganese by Oxidation, Detention, and Filtration
1) Oxidation
must be by aeration, as indicated in Subpart D, unless the community water
supply demonstrates chemical oxidation provides equivalent results to
aeration. Chemicals that may be used for oxidation include chlorine, sodium
permanganate, potassium permanganate, ozone, or chlorine dioxide.
2) Detention
A) A
minimum detention time of 30 minutes must be provided following aeration to
ensure that the oxidation reactions are complete prior to filtration. This
minimum detention time may be modified only when a pilot plant study indicates
completion of oxidation reactions in less time.
B) The
reaction tank/detention basin must be provided with an overflow, vents, and
access hatches in accordance with Subpart M.
3) Filtration.
Filters must conform to Subpart F.
c) Removal
by Manganese Greensand or Manganese Coated Media Filtration
1) Permanganate
or chlorine must be added to the water upstream of the filter, per the manufacturer's
recommendation.
2) An
anthracite media cap of at least six inches must be provided over manganese
greensand.
3) Normal
backwash rate is 8 gal/min/ft
2
with filters containing manganese
greensand and 15 gal/min with manganese coated media.
4) Sample
taps must be provided:
A) prior
to application of permanganate;
B) immediately
ahead of filtration;
C) at
points between the anthracite media and the manganese greensand;
D) halfway
down the manganese greensand; and
E) at the
filter effluent.
d) Sequestration of Iron or
Manganese by Polyphosphates
1) Sequestration
by polyphosphates must not be used when the combination of iron and manganese
exceeds 1 mg/L.
2) Phosphate
solution must be kept covered and disinfected by carrying approximately 10 mg/L
free chlorine residual unless the phosphate is not able to support bacterial
growth and the phosphate is being fed from the covered shipping container.
Phosphate solutions having a pH of 2.0 or less may also be exempted from this
requirement by the Agency.
3) Polyphosphates
must not be applied ahead of iron and manganese removal treatment. The point
of application must be prior to aeration, oxidation, or disinfection.
4) The
phosphate feed point must be located as far ahead of the oxidant feed point as
possible.
e) Sequestration of Iron or
Manganese by Sodium Silicates:
1) Sequestration
by sodium silicate must not be used when iron, manganese, or a combination of
iron and manganese exceeds 2 mg/L.
2) A
full-scale demonstration will be required to determine the suitability of
sodium silicate for the particular water and the minimum feed needed.
3) Chlorine
or chlorine dioxide addition must accompany the sodium silicate addition.
4) Sodium
silicate must not be applied ahead of iron or manganese removal treatment.