35 Ill. Adm. Code 6040.604.1425
Hydrants
TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE F: PUBLIC WATER SUPPLIES
CHAPTER I: POLLUTION CONTROL BOARD
PART 604 DESIGN, OPERATION, AND MAINTENANCE CRITERIA
SECTION 604.1425 HYDRANTS
Section 604.1425 Hydrants
a)
Only water mains designed to carry fire flows may have fire hydrants
connected to them.
1) The
fire hydrant lead must be a minimum of six inches in diameter.
2) Auxiliary valves must
be installed on all fire hydrant leads.
b) Unless
otherwise approved by the Agency under Section 604.145(b), water mains not
designed to carry fire flows must have flushing hydrants.
1) Flushing
hydrants must be sized to provide flows that will give a velocity of at least
2.5 feet per second in the water main being flushed.
2) No
flushing device may be directly connected to any sewer.
c) Each
community water supply must develop and maintain a systematic flushing program.
d) Hydrant Drainage
1) When
hydrant drains are plugged, the barrels must be pumped dry after use during
freezing weather.
2) When
hydrant drains are not plugged, a gravel pocket or dry well must be provided
unless the natural soils will provide adequate drainage.
3) Hydrant
drains must not be connected to or located within 10 feet of sanitary sewers,
storm sewers, or storm drains.
4) Hydrant
drains must be above the seasonal groundwater table.