35 Ill. Adm. Code 6040.604.525
Tube or Plate Settlers
TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE F: PUBLIC WATER SUPPLIES
CHAPTER I: POLLUTION CONTROL BOARD
PART 604 DESIGN, OPERATION, AND MAINTENANCE CRITERIA
SECTION 604.525 TUBE OR PLATE SETTLERS
Section 604.525 Tube or Plate Settlers
a) Settler
units consisting of variously shaped tubes or plates installed in multiple
layers and at an angle to the flow may be used for sedimentation, following
flocculation.
b) Tube or plate settlers
must meet the following requirements:
1) Inlet
and outlet design must maintain velocities suitable for settling in the basin
and to minimize short-circuiting;
2) Plate
units must be designed to minimize maldistribution across the units;
3) Drain
piping from settler units must be sized to facilitate a quick flush of the settler
units and to prevent flooding of other portions of the plant;
4) Outdoor
installations must be protected against freezing, including sufficient
freeboard above the top of the settlers;
5) Tubes
must have a maximum application rate of 2 gpm per square foot of
cross-sectional area, unless higher rates are shown through pilot plant or
in-plant demonstration studies;
6) Plates
must have a maximum application rate of 0.5 gpm per square foot, based on 80
percent of the projected horizontal plate area;
7) Flushing
lines must be provided to facilitate maintenance and must be properly protected
against backflow or back-siphonage;
8) Inlets
and outlets must conform with Section 604.515(b) and (d);
9) The
units' support system must be able to carry the weight of the settler units
when the basin is drained plus any additional weight to support maintenance;
and
10) Settler
units must accommodate:
A) A
water or air jet system for cleaning their tubes or plates; and
B) Dropping
their water level to allow cleaning with the system identified in subsection
(b)(10)(A).