35 Ill. Adm. Code 506.202
Site Investigation
Section 506
Section 506.202 Site
Investigation
a) The owner or operator of a lagoon constructed under this
Subpart must conduct a site investigation in compliance with this Section to
determine the following:
1) Whether aquifer material is considered present (or not
present) within 50 feet of the planned bottom of the lagoon;
2) Whether the proposed lagoon is to be located within the
floodway or flood fringe of a 100-year floodplain; and
3) Whether the proposed lagoon is to be located within a karst
area or within 400 feet of a natural depression in a karst area.
b) The owner or operator must perform one or more soil borings
that must be located within the final lagoon area or within 20 feet of the
final exterior berm toe. The boring must be performed to determine the
presence of aquifer material or karstified carbonate bedrock as follows:
1) The soil boring must extend to a depth that includes 50 feet
below the planned bottom of lagoon native soil or to bedrock;
2) If bedrock is encountered, additional soil borings may be
necessary to verify the presence of aquifer material or karstified carbonate
bedrock;
3) Continuous samples must be recovered from each soil boring;
and
4) Upon completion, the borings must be properly abandoned and
sealed under the Illinois Water Well Construction Code at 77 Ill. Adm. Code
920.120.
c) If the Department determines that additional soil borings are
necessary to ensure the protection of the groundwater, the surface water, or
the structural integrity of the livestock waste management facility, the
Department must require additional soil borings.
d) As an alternative to performing the soil borings required
under subsection (b) or (c), the owner or operator of the lagoon may propose to
the Department to use alternative information sources. The Department must
evaluate the proposal; determine whether the alternative information sources
will result in a site investigation that will be at least as protective of the
groundwater, the surface water, and the structural integrity of the livestock
waste management facility as would have resulted from data resulting from soil
borings; and notify the owner or operator of the Department's finding.
e) Despite the other requirements of this Subpart, if the site
investigation determines that the lagoon is to be located in the flood fringe
of a 100-year floodplain, the design of the lagoon must comply with Section
506.206.
f) If the results of the soil boring conducted under Section
506.202(b) indicate the proposed lagoon is to be located in a karst area or if
the proposed lagoon is to be located within an area designated as "Sink
hole areas" on "Karst Terrains and Carbonate Rocks of Illinois",
IDNR-ISGS Illinois Map 8, the following requirements must be met:
1) The Department must conduct a visual inspection of the
surrounding area to determine the presence of natural depressions during the
pre-construction site inspection as required under 8 Ill. Adm. Code 900.604(a).
Construction must not occur within 400 feet of a natural depression in a karst
area; and
2) The Licensed Professional Engineer or Licensed Professional
Geologist must evaluate the results of the soil boring conducted under
subsection (b). If the soil boring reveals a void of 1 foot or greater in
vertical distance, the following requirements must be met:
A) The Department may require additional borings to determine the
extent of the void;
B) Despite the other requirements of this Subpart, the owner or
operator must submit to the Department a plan for the design of the lagoon that
must include the additional design requirements stated in Section 506.207 and must
include any additional design requirements necessary by the Licensed
Professional Engineer; and
C) The Department must review and approve the plan required under
subsection (f)(2)(B) before construction. The Department may also require
additional design criteria before the plan is approved and construction may
begin. If no voids of 1 foot or greater are discovered from the soil boring
performed, the design must include the additional requirements in Section
506.207.
g) The site investigation in compliance with subsection (b), (c),
(d), (e), or (f) must be conducted under the direction of a Licensed
Professional Engineer or Licensed Professional Geologist.