35 Ill. Adm. Code 602.255

Storage Construction Applications

Last amended: 2019Year: 2026Length: 165 wordsOfficial source
Section 602.255  Storage Construction Applications The following information must be submitted on plans for the construction of storage facilities: a)         storage capacity; b)         plan and profile views showing the location, elevation, piping, access hatches, vents, overflows, safety appurtenances and sample taps; c)         for below ground or partially below ground storage tanks, locations of the sources of pollution listed in 35 Ill. Adm. Code 604.150(a) within a 400-foot radius of the storage structure; d)         security provisions; e)         baffling arrangement, if applicable; f)         for sites subject to flooding, the maximum flood level based upon the highest flood level specified in the best available information, such as the flood of record, the 100-year flood projection or the 500-year flood projection; g)         for hydropneumatic tanks, the bypass piping, access manhole, drain, sight glass, pressure gauge, pressure relief valve, air compressor and housing; h)         mixing systems, if applicable; and i)          the ability to drain a storage tank without causing the pressure in the distribution system to drop below 20 psi.