35 Ill. Adm. Code 604.1210
Pumps
Section 604.1210Â Pumps
a)Â Â Â Â Â Â Â Â At least two pumping
units must be provided for all pump stations.
b)Â Â Â Â Â Â Â Â With
any pump out of service, the remaining pump or pumps must be capable of
providing the maximum demand of the community water supply.
c)Â Â Â Â Â Â Â Â The
pumping units must be provided with readily available spare parts and tools.
d)Â Â Â Â Â Â Â Â Suction
Lifts
1)Â Â Â Â Â Â Â Â Suction lifts must be
avoided if possible;
2)Â Â Â Â Â Â Â Â Suction
lifts must be less than 15 feet; and
3)Â Â Â Â Â Â Â Â If
suction lift is necessary, provisions must be made for priming the pumps, as
follows:
A)Â Â Â Â Â Â Â prime
water must not be of lesser sanitary quality than that of the water being
pumped;
B)Â Â Â Â Â Â Â means
must be provided to prevent either backsiphonage or backflow; and
C)Â Â Â Â Â Â Â vacuum
priming may be used.
e)Â Â Â Â Â Â Â Â Pumps
taking suction from ground storage tanks must be provided adequate net positive
suction head, but the minimum distribution pressure of 20 psi is not required.Â
The pumps must be equipped with automatic shutoffs or low-pressure controllers,
as recommended by the pump manufacturer.