35 Ill. Adm. Code 604.1315
Vents
Section 604.1315Â Vents
a)Â Â Â Â Â Â Â Â Finished water storage
structures must be vented as follows:
1)Â Â Â Â Â Â Â Â the
overflow pipe must not be considered a vent; and
2)Â Â Â Â Â Â Â Â open
construction between the sidewall and roof is not permissible.
b)Â Â Â Â Â Â Â Â Vents must:
1)Â Â Â Â Â Â Â Â prevent the entrance of
surface water and rainwater;
2)Â Â Â Â Â Â Â Â exclude birds and
animals;
3)Â Â Â Â Â Â Â Â exclude
insects and dust to the extent practicable;
4)Â Â Â Â Â Â Â Â on
ground level structures, open downward with the opening at least 24 inches
above the roof or sod and be covered with 24 mesh non-corrodible screen; and
5)Â Â Â Â Â Â Â Â on
elevated tanks and standpipes:
A)Â Â Â Â Â Â Â open
downward; and
B)Â Â Â Â Â Â Â be
fitted with either four mesh non-corrodible screen, or with finer mesh
non-corrodible screen in combination with an automatically resetting
pressure-vacuum relief mechanism, as required by the Agency.