35 Ill. Adm. Code 604.1325
Roof and Sidewalls
Section 604.1325Â Roof and Sidewalls
a)Â Â Â Â Â Â Â Â The
roof and sidewalls of all water storage structures must be watertight with no
openings except properly constructed vents, manholes, overflows, risers,
drains, pump mountings, control ports, or piping for inflow and outflow.
b)Â Â Â Â Â Â Â Â Any
pipes running through the roof or sidewall of a metal storage structure must be
welded or gasketed to prevent leaks.
c)Â Â Â Â Â Â Â Â Any
pipes running through the roof or sidewall of a concrete tank must be connected
to standard wall castings that were poured in place during the forming of the
concrete.
d)Â Â Â Â Â Â Â Â Openings
in the roof of a storage structure designed to accommodate control apparatus or
pump columns must be curbed and sleeved with proper additional shielding to
prevent contamination from surface or floor drainage.
e)Â Â Â Â Â Â Â Â The
roof of the storage structure must be well drained.
1)Â Â Â Â Â Â Â Â Downspout pipes must
not enter or pass through the reservoir.
2)Â Â Â Â Â Â Â Â Parapets,
or similar construction that would tend to hold water and snow on the roof,
must have adequate waterproofing and drainage.
f)Â Â Â Â Â Â Â Â The
roof of concrete reservoirs with earthen cover must be sloped to facilitate
drainage and must have an impermeable membrane roof covering.
g)Â Â Â Â Â Â Â Â Reservoirs
with pre-cast concrete roof structures must be made watertight with the use of
a waterproof membrane or similar product.
h)Â Â Â Â Â Â Â Â The
installation of appurtenances, such as antenna, must be done in a manner that
ensures no damage to the tank, coatings or water quality, or corrects any
damage that occurred.