35 Ill. Adm. Code 604.1430
Air Relief Valves
Section 604.1430 Air Relief Valves
a)Â Â Â Â Â Â Â Â Air
relief valves must be installed at high points in water mains where air can
accumulate.
b)Â Â Â Â Â Â Â Â Automatic
air relief valves must not be used in situations where flooding of the manhole
or chamber may occur.
c)Â Â Â Â Â Â Â Â Air Relief Valve Piping
1)Â Â Â Â Â Â Â Â The
open end of an air relief pipe from a manually operated valve must extend to
the top of the pit and be provided with a screened, downward-facing elbow if
drainage is provided for the manhole.
2)Â Â Â Â Â Â Â Â The
open end of an air relief pipe from automatic valves must be extended to at
least one foot above grade and provided with a screened, downward‑facing
elbow.
3)Â Â Â Â Â Â Â Â Discharge
piping from air relief valves must not connect directly to any storm drain,
storm sewer, or sanitary sewer.