35 Ill. Adm. Code 604.1505
Cross Connection Control Program
Section 604.1505Â Cross Connection Control Program
a)Â Â Â Â Â Â Â Â All
community water supplies, including those that meet the criteria in Section
17(b) of the Act and any exempt community water supply as defined in Section
9.1 of the Public Water Supply Operations Act [415 ILCS 45], must have a cross
connection control program to educate and inform water supply consumers
regarding prevention of the entry of contaminants into the distribution
system.
b)Â Â Â Â Â Â Â Â The
cross connection control program must include the following:
1)Â Â Â Â Â Â Â Â For
any new service connection, the community water supply must evaluate the risk
of cross connection whereby an unsafe substance may enter a community water
supply.
2)Â Â Â Â Â Â Â Â A
community water supply must conduct a cross connection control survey of the
distribution system at least every three years. The survey must be conducted
by the owner, official custodian or an authorized delegate. The survey must
evaluate the risk of an unsafe substance entering a community water supply
through each service connection to the distribution system of the community
water supply. This survey is not intended to include an actual visual
inspection of piping or plumbing systems.
3)Â Â Â Â Â Â Â Â From
each completed survey, the community water supply must develop an inventory of
the following:
A)Â Â Â Â Â Â Â all customers surveyed;
B)Â Â Â Â Â Â Â the number of customers
who responded to the survey;
C)Â Â Â Â Â Â Â identification
of service connections not required to have a backflow preventer installed under
77 Ill. Adm. Code 890.1130;
D)Â Â Â Â Â Â Â identification
of service connections required to have a backflow preventer installed under 77
Ill. Adm. Code 890.1130;
E)Â Â Â Â Â Â Â backflow
preventers installed;
F)Â Â Â Â Â Â Â Â service connections
that require further risk evaluation; and
G)Â Â Â Â Â Â Â corrective
actions to mitigate cross connections.
4)Â Â Â Â Â Â Â Â An
ordinance, tariff, or required condition for service, whichever is applicable, that
meets the Illinois Plumbing Code (77 Ill. Adm. Code 890), must be adopted and
enforced.
5)Â Â Â Â Â Â Â Â The
community water supply must maintain records of all backflow preventers that
require annual testing under 77 Ill. Adm. Code 890 and identified in subsections
(b)(2) and (b)(3).