35 Ill. Adm. Code 604.620
Biologically Active Filtration
Section 604.620 Biologically Active Filtration
Biologically active filtration refers to the filtration of
surface water or a groundwater with iron, manganese or significant natural
organic material, which includes the establishment and maintenance of
biological activity within the filtration media. The objectives of
biologically active filtration may include control of disinfection byproduct
precursors; increased disinfectant stability; reduction of substrates for
microbial regrowth; breakdown of small quantities of synthetic organic
chemicals; and oxidation of ammonia-nitrogen, iron and manganese. Biological
activity can have an adverse impact on turbidity, particle and microbial
pathogen removal, disinfection practices, head loss development, and filter run
times and distribution system corrosion.
a) Before
use of biologically active filters, the community water supply must conduct a
pilot study and obtain Agency approval. Pilot study objectives must be clearly
defined and must ensure the microbial quality of the filtered water under all
anticipated conditions of operation.
1) The
pilot study must be of sufficient duration to ensure establishment of full
biological activity; often greater than three months is required.
2) The
pilot study must establish empty bed contact time, surface filtration hydraulic
loading rate, substrate loading rate per unit filter media volume, and
treatment efficiency for removal or reduction of concentration of parameters
targeted for the pilot study.
b) The
final filter design must be based on the pilot plant studies and must comply
with Section 604.605.