35 Ill. Adm. Code 604.705
Chlorination Equipment
Section 604.705 Chlorination Equipment
a) Procedure
for Submitting Plans and Specifications − Design documents for
chlorination must be prepared and submitted in accordance with 35 Ill. Adm.
Code 602.
b) Chlorination equipment
must:
1) be
large enough to satisfy the immediate chlorine demand and give a measurable
residual of at least 2.0 mg/L of total chlorine under all operating conditions
after contact;
2) be
capable of feeding chlorine to the water being treated at a dosage rate of at
least 5.0 mg/L, except when the water has a high chlorine demand. Factors in
determining chlorine demand are:
A) pH;
B) water temperature;
C) contact time;
D) presence
in the water of substances having chlorine demand such as hydrogen sulfide,
iron, manganese and nitrogenous compounds including ammonia; and
E) supplemental
treatment such as aeration that reduces chlorine demand;
3) be
provided in duplicate when operating conditions do not allow repair of the
chlorinator during off-pumping periods;
4) be
provided in duplicate, installed and operational, at community water supplies
treating surface water, groundwater under the direct influence of surface
water, and groundwater with a history of total coliform positive results; and
5) include
spare parts for emergency repairs consisting of at least the commonly
expendable parts such as glassware, fittings, hose clamps, and gaskets.