35 Ill. Adm. Code 6110.611.352
Corrosion Control Treatment
Section 611
TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE F: PUBLIC WATER SUPPLIES
CHAPTER I: POLLUTION CONTROL BOARD
PART 611 PRIMARY DRINKING WATER STANDARDS
SECTION 611.352 CORROSION CONTROL TREATMENT
Section 611.352 Corrosion
Control Treatment
Description of corrosion control
treatment requirements. This section provides the requirements for suppliers
and the Agency designating optimal corrosion control treatment (OCCT) for a
supplier that is optimizing or re-optimizing OCCT. All suppliers must complete
the corrosion control treatment requirements in this Section as applicable
under Section 611.351.
a) Supplier recommendation regarding corrosion control treatment.
1)
Any supplier
without corrosion control treatment that is required to
recommend a treatment option in compliance with Section 611.351(e)
(1)(C) must, based on the results of lead and copper tap
sampling and water quality parameter monitoring, recommend designating one or
more of the corrosion control treatments in subsection(c)(1) to
the Agency as
the optimal corrosion control treatment for that supplier. The Agency may
require the supplier to conduct additional water quality parameter monitoring
to assist the Agency in reviewing the supplier's recommendation.
2)
Any supplier with corrosion control
treatment that exceeds the lead action level that is required to recommend a
treatment option to the Agency in compliance with Section 611.351(d)(1)(C) must
recommend designating one or more of the corrosion control treatments listed in
subsection (c)(2) as the optimal corrosion control treatment for that supplier.
3) The Agency may waive the requirement for a supplier to
recommend OCCT if the Agency requires the supplier, in writing, to complete a
corrosion control study within three months after the end of the tap sampling
period in which the lead or copper action level exceedance occurred. These suppliers
must proceed directly to subsection (c) and complete a corrosion control study.
b) Agency-decision to require studies to identify initial OCCT
under Section 611.351.(e)(2) and re-optimized OCCT under Section 611.351(d)(2).
1) The Agency may require any small or medium supplier without
corrosion control treatment that exceeds either the lead action level or copper
action level to perform corrosion control treatment studies under subsection
(c)(1) to identify OCCT for the supplier's system.
2) The Agency may require any small or medium supplier with
corrosion control treatment exceeding either the lead or copper action level to
perform corrosion control treatment studies under subsection (c)(2) to identify
re-optimized OCCT for its system (i.e., OCCT after a re-optimization evaluation).
c) Performing corrosion control studies.
1)
Suppliers without
corrosion control treatment
required to conduct corrosion control studies
under
subsection 611.351(e) must evaluate the effectiveness of each of the following
treatments, and if appropriate, combinations of the following treatments to
identify OCCT for the system:
A) Alkalinity and pH adjustment;
B) The addition of an orthophosphate- or silicate-based corrosion
inhibitor at a concentration sufficient to maintain an effective corrosion
inhibitor residual concentration in all test samples;
C) The addition of an orthophosphate-based corrosion inhibitor at
a concentration sufficient to maintain an orthophosphate residual concentration
of 1 mg/ L (as PO
4
) in all test samples; and
D) The addition of an orthophosphate-based corrosion inhibitor at
a concentration sufficient to maintain an orthophosphate residual concentration
of 3 mg/ L (as PO
4
) in all test samples.
2)
Suppliers with corrosion control treatment
required to conduct corrosion control studies under Section 611.351(d) must
evaluate the effectiveness of the following treatments, and if appropriate,
combinations of the following treatments, to identify re-optimized OCCT for the
system:
A) Alkalinity
and/or pH adjustment or re-adjustment;
B) The
addition of an orthophosphate- or a silicate-based corrosion inhibitor at a
concentration sufficient to maintain an effective corrosion inhibitor residual
concentration in all test samples if no such inhibitor is currently utilized;
C) The
addition of an orthophosphate-based corrosion inhibitor at a concentration
sufficient to maintain an orthophosphate residual concentration of 1 mg/ L (PO
4
)
in all test samples unless the current inhibitor process already meets this
residual; and
D) The
addition of an orthophosphate-based corrosion inhibitor at a concentration
sufficient to maintain an orthophosphate residual concentration of 3 mg/L (as
PO
4
) in all test samples unless the current inhibitor process
already meets this residual.
3) Suppliers must evaluate each of the corrosion control
treatments in subsection (c)(1) or (2) individually or, if appropriate, in
combinations, using pipe rig/loop tests, metal coupon tests, partial-system
tests, and/or analyses based on documented analogous treatments with similar
size systems that have a similar water chemistry, and similar distribution
system configurations. Large and medium suppliers with lead service lines and
other systems as required by the Agency, that exceed the lead action level must
conduct pipe rig/loop studies using harvested lead service lines from their
distribution systems to assess the effectiveness of corrosion control treatment
options on the existing pipe scale. Metal coupon tests can be used as a screen
to reduce the number of options evaluated in the pipe rig/loop studies to the
current water quality and at least two additional treatment options.
4) Suppliers must measure the following water quality parameters
in any tests conducted under subsection (c)(3) both before and after evaluating
the corrosion control treatments listed in subsections (c)(1) or (c)(2):
A Lead;
B) Copper;
C) pH;
D) Alkalinity;
E) Orthophosphate as PO
4
(when an orthophosphate-based
inhibitor is used);
F) Silicate (when a silicate-based inhibitor is used); and
G) Any additional parameters necessary to evaluate the
effectiveness of a corrosion control treatment as determined by the Agency.
5) Suppliers must identify all chemical or physical constraints that
limit or prohibit the use of a particular corrosion control treatment and
document those constraints by providing either of the following:
A) Data and documentation showing a particular corrosion control
treatment has adversely affected other drinking water treatment processes when used
by another supplier with comparable water quality characteristics. Suppliers
using metal coupon tests to screen and/or pipe rig/loop studies to evaluate
treatment options cannot exclude treatment strategies from the studies based on
the constraints identified in subsection (c)(5)(A).
B) Data and documentation demonstrating the supplier previously attempted
to evaluate a particular corrosion control treatment and found the treatment was
ineffective or adversely affects other drinking water quality treatment
processes. Suppliers using metal coupon tests to screen and/or pipe rig/loop
studies to evaluate treatment options cannot exclude treatment strategies from
the studies based on the constraints identified in subsection (c)(5)(B), unless
the treatment was found to be ineffective in a previous pipe rig/loop study.
6) Suppliers must evaluate the effect of the chemicals used for
corrosion control treatment on other drinking water quality treatment
processes. Suppliers using metal coupon tests to screen and/or pipe rig/loop/
studies to evaluate treatment options cannot exclude any of the required treatment
strategies specified in subsection (c)(1) or (c)(2) from the studies based on
the effects identified in this Section.
7) Based on the data and analysis for each treatment option
evaluated under this subsection (c), suppliers must recommend to the Agency, in
writing, the treatment option that the corrosion control studies indicate
constitutes OCCT for its system as defined in Section 611.350(b). Suppliers
must provide the Agency with a rationale for the OCCT recommendation, and all
supporting documentation specified in subsections (c)(1) or (c)(2) and
subsections (c)(3) through (c)(7).
d) Agency designation of OCCT and re-optimized OCCT
1)
Designation of OCCT or re-optimized
OCCT. Based on available information, including, where applicable, studies conducted
under subsection (c)(1) or (c)(2) and/or a supplier's recommended corrosion
control treatment option, the Agency must either approve the
supplier-recommended corrosion control treatment option or designate
alternative corrosion control treatment(s) from among those listed in
subsection (c)(1) or (c)(2), as applicable. The Agency must notify the
supplier, in writing, of its designation of OCCT or re-optimized OCCT and
explain the basis for this determination.
A) When designating OCCT, the Agency must consider the effects
that additional corrosion control treatment has on water quality parameters and
other drinking water quality treatment processes.
B) If the Agency requests additional information to aid its
review, the supplier must provide that information.
2)
This subsection (d)(2) corresponds
with 40 CFR 141.82(d)(2), which USEPA marked "Reserved". This
statement maintains structural consistency with USEPA's rule.
e) Installing OCCT and Re-Optimizing OCCT. Each supplier must
install and operate the OCCT or re-optimized OCCT designated by the Agency
under subsection (d) throughout its distribution system.
f) Agency review of treatment and designation of optimal water
quality parameters for OCCT and re-optimized OCCT. The Agency must evaluate
the results of all lead and copper tap and water quality parameter sampling submitted
by the supplier and determine whether the supplier has installed and operated
the OCCT designated by the Agency in subsection (d). Upon reviewing the
supplier's tap and water quality parameter sampling results, both before and
after the supplier installs OCCT, or re-optimized OCCT, the Agency must designate
each of the following:
1) A minimum value or a range of values for pH measured at each
entry point to the distribution system.
2) A minimum pH value measured in all distribution system
samples. This value must be equal to or greater than 7.0, unless the Agency
determines that meeting a pH level of 7.0 is not technologically feasible or is
not necessary for OCCT.
3) If a corrosion inhibitor is used, a minimum concentration or a
range of concentrations for orthophosphate (as PO
4
) or silicate
measured at each entry point to the distribution system.
4) If a corrosion inhibitor is used, a minimum orthophosphate (as
PO
4
) or silicate concentration measured in all tap samples that the Agency
determines is necessary to form a passivating film on the interior walls of the
pipes of the distribution system. When orthophosphate is used, for OCCT
designations for suppliers previously without corrosion control treatment, the
orthophosphate concentration must be equal to or greater than 0.5 mg/L (as PO
4
)
and for OCCT designations for suppliers previously with corrosion control
treatment, the orthophosphate concentration must be equal to or greater than 1.0
mg/L, unless the Agency determines that meeting the applicable minimum
orthophosphate residual is not technologically feasible or is not necessary for
OCCT.
5) If alkalinity is adjusted as part of OCCT, a minimum
concentration or a range of concentrations for alkalinity, measured at each
entry point to the distribution system and in all tap samples.
6) The values for the applicable water quality parameters in subsections
(f)(1) through (f)(5) must be the values the Agency determines reflect OCCT or
re-optimized OCCT for the supplier's water system. The Agency may designate
values for additional water quality parameters the Agency determines reflect
OCCT or re-optimized OCCT for the supplier's water system. The Agency must
notify the supplier, in writing, of these determinations and explain the basis
for its decisions.
g) Continued operation and monitoring for OCCT and re-optimized
OCCT. All suppliers, including those optimizing or re-optimizing OCCT, must
continue to operate and maintain OCCT, including maintaining water quality parameters
at or above the minimum values or within the ranges designated by the Agency under
subsection (f), in compliance with this subsection (g) for all water quality
parameter samples collected under Section 611.357(b)(4) through (d). The
requirements of this subsection (g) apply to all suppliers, including
suppliers with consecutive systems that distribute water
that has been treated to control corrosion by another supplier,
and any supplier system with
corrosion
control treatment
,OCCT,
or re-optimized OCCT that is not required to
monitor water quality parameters under Section 611.357.
1) The supplier must determine whether it complies with this
subsection (g) every six months, as specified in Section 611.357(b)(4). A supplier
is out of compliance with this subsection (g) for a six-month period if it has
excursions for any Agency-specified parameter on more than nine days,
cumulatively, during the period. An excursion occurs whenever the daily value
for one or more of the water quality parameters measured at a sampling location
is below the minimum value or outside the range designated by the Agency. Daily
values are calculated as set out in subsection (g)(2). The Agency has
discretion to not include results of obvious sampling errors from this
calculation. The supplier must record sampling errors even when not included in
calculations.
2) Water quality parameter daily value.
A) On days when the supplier collects more than one measurement
for a water quality parameter at a sampling location, the daily value must be
the average of all results collected at that sampling location during the same day,
regardless of whether they are collected through continuous monitoring, grab
sampling, or a combination of both.
BOARD NOTE:
Corresponding 40 CFR 141.82(g)(2)(i) further provides as follows: If USEPA
approves an alternative formula under 40 CFR 142.16(d)(1)(ii) in the State's
application for a program revision submitted under 40 CFR 142.12, the approved
formula must be used to aggregate multiple measurements at a sampling point for
the water quality parameters in lieu of the formula in this subsection (g)(2).
B) On days when the supplier collects only one measurement for a
water quality parameter at a sampling location, the daily value must be the
result of that measurement.
C) On days when the supplier collects no measurement for a water
quality parameter at a sampling location, the daily value must be the daily
value calculated on the most recent day on which the supplier measured the
water quality parameter at the sampling location.
h) Modification of Agency treatment determination for OCCT and
re-optimized OCCT. Upon its own initiative or in response to a request by a
supplier or other interested party, the Agency may modify its determination of
OCCT under subsection (d), or the optimal water quality parameters under
subsection (f). A request for modification by a supplier or other interested
party must be in writing, explaining why the modification is appropriate, and
providing supporting documentation. The Agency may require a supplier to
conduct a CCT study to support modification of the determination of OCCT or
re-optimized OCCT. The Agency may modify its determination
where it concludes
that such a change is
necessary to ensure that the supplier continues to optimize corrosion control
treatment. A revised designation must be made in writing, set forth the new
treatment requirements and/or optimal water quality parameters, explain the
basis for the Agency's determination, and provide an implementation schedule
for completing the treatment modifications for re-optimized corrosion control
treatment.
i) Treatment decisions by USEPA in lieu of the Agency on OCCT
and re-optimized OCCT. Under the procedures in 40 CFR 142.19, USEPA may review
OCCT determinations made by the Agency under subsections
(d),(f),
or (h) and issue federal corrosion control treatment determinations
consistent with the requirements of 40 CFR 141.82(d), (f), or (h) where USEPA
finds that:
1) The Agency failed to issue a treatment determination by the
applicable deadlines in Section 611.351 (corresponding with 40 CFR 141.81);
2) The Agency abused its discretion; or
3) The technical aspects of the Agency's determination would be
indefensible in a federal enforcement action taken against a supplier.
j)
Distribution system and site assessment for
tap sampling sites with lead results that exceed 0.010 mg/L. T
he supplier must conduct the following steps
when the
lead results from an individual tap sample site sampled under Section 611.356
exceed 0.010 mg/L and the site is included in the site sample plan under
Section 611.356(a)(1):
1)
Step 1: Corrosion control treatment assessment
.
Within five days of receiving the tap sampling results, the supplier must
sample at a water quality parameter site in compliance with subsection
(j)(1)(B) that is on the
same-size water main, in the
same pressure zone and located within a half mile radius of the site
with the lead result that exceeds 0.010 mg/L. Suppliers
without
corrosion control treatment
are not required to collect these samples.
A) The
supplier must measure the following water quality parameters:
i) pH;
ii) Alkalinity;
iii) Orthophosphate (as PO
4
), when an inhibitor
containing an orthophosphate compound is used; and
iv) Silica, when an inhibitor containing a silicate compound is
used.
B) The
supplier must measure at the following locations:
i) Suppliers with an existing water quality parameter site that
meets the requirements in this subsection (j)(1) can conduct this sampling at
that site.
ii) All
suppliers required to meet optimal water quality parameters but do not have an
existing water quality parameter site that meets the requirements in this
subsection (j)(1) must add new sites to the minimum number of sites described
in Section 611.357(b)(1)(A). Sites must be added until a supplier has twice
the minimum number of sites listed in Section 611.357(b)(1)(A). When a
supplier exceeds twice the number of sites, the Agency has discretion to
determine if these additional newer sites can better assess the effectiveness
of the corrosion control treatment and whether to remove existing sites during
sanitary survey evaluation of OCCT.
2)
Step 2: Site assessment
.
Within 30 days of receiving the tap sampling results,
suppliers
must collect
and analyze a follow-up
sample for lead at
any tap sample site that exceeds
0.010
mg/L .
T
he supplier may
use these follow-up sample volumes or different sample procedures
to assess
the source of elevated lead levels.
Samples the
supplier collected
under this Section
must be
submitted to the Agency but cannot be included in
the
90
th
percentile calculation
for compliance
monitoring under Section 611.356. I
f the supplier is unable to collect a follow-up sample
at a site,
the supplier must
provide documentation
to the Agency, as specified in Section 611.360(g)(2), explaining why it was
unable to collect a follow-up sample.
3)
Step 3:
Evaluate results and system
treatment recommendation. Suppliers must evaluate the results of
the sampling conducted under subsections (j)(1)
and
(j)(2) to determine if either localized or centralized adjustment of
OCCT
or other distribution system actions are
necessary and submit the recommendation to the Agency within six months after
the end of the tap sampling period in which the site(s) exceeded 0.010 mg/L.
Corrosion
control treatment
modification
may not be necessary to address every exceedance of 0.010 mg/L. Other distribution
system actions may include flushing to
reduce water
age. Suppliers
must note the cause of the elevated lead level, if known
from the site assessment, in their recommendation to the Agency as
site-specific issues can be an important factor in why the supplier does not
recommend any adjustment of corrosion control treatment or other distribution
system actions. Suppliers in the process of
optimizing
or re-optimizing
OCCT under subsections (a) through (f)
do not need to submit a treatment recommendation for
distribution system and site assessment
.
4) Step
4: Agency approval of treatment recommendation. T
he
Agency must approve the supplier's treatment recommendation
or specify a
different approach
within six months of completing Step
3, as described in subsection (j)(3)
and notify the supplier in writing.
5) Step
5
:
Modifications to OCCT. I
f the Agency-
approved treatment recommendation
requires
the supplier to
adjust
the
OCCT process, the supplier
must
complete modifications to its corrosion control treatmen
t
within 12 months
of receiving notification from the
Agency, as described in subsection (j)(4).
Suppliers
without
corrosion control treatment required to
install OCCT
must follow the schedule in Section 611.351(e).
6) Step
6:
Follow-up sampling
.
Suppliers
adjusting OCCT
must complete follow-up sampling in
compliance with Sections 611.356(c)(2)(C)(iv) and 611.357(b)(3) within 12
months after completing Step 5, as described in subsection (j)(5) and submit
sampling results to the Agency in compliance with Sections 611.356 and 611.357.
7) Step
7: Agency OWQP designation. F
or suppliers adjusting
OCCT
,
the Agency must
review the supplier's modification of corrosion control treatment and designate
optimal water quality parameters in compliance with subsection (f) within six
months of receiving the sampling result described in subsection (j)(6).
8) Step
8: Operate in compliance.
For a supplier adjusting
OCCT,the
supplier must comply with the Agency-designated optimal water quality
parameters in compliance with subsection (g) and
continue
to conduct tap sampling
in compliance with Sections 611.356(c)(2)(C)(v) and
611.357(b)(4).
BOARD NOTE: This Section
derives from 40 CFR 141.82.