SECTION 611.385 TREATMENT TECHNIQUE FOR CONTROL OF DISINFECTION BYPRODUCT (DBP) PRECURSORS
Section 611.385 Treatment
Technique for Control of Disinfection Byproduct (DBP) Precursors
a) Applicability
1) A Subpart B system supplier using conventional filtration
treatment (as defined in Section 611.101) must operate with enhanced
coagulation or enhanced softening to achieve the TOC percent removal levels
specified in subsection (b) unless the supplier meets at least one of the alternative
compliance standards listed in subsection (a)(2) or (a)(3).
2) Alternative compliance standards for enhanced coagulation and
enhanced softening systems. A Subpart B system supplier using conventional
filtration treatment may use the alternative compliance standards in
subsections (a)(2)(A) through (a)(2)(F) to comply with this Section in lieu of
complying with subsection (b). A supplier must comply with monitoring
requirements in Section 611.382(d).
A) The supplier's source water TOC level, measured according to
Section 611.381(d)(3), is less than 2.0 mg/ℓ, calculated quarterly as a
running annual average.
B) The supplier's treated water TOC level, measured according to
Section 611.381(d)(3), is less than 2.0 mg/ℓ, calculated quarterly as a
running annual average.
C) The supplier's source water TOC level, measured according to
Section 611.381(d)(3), is less than 4.0 mg/ℓ, calculated quarterly as a
running annual average; the source water alkalinity, measured according to
Section 611.381(d)(1), is greater than 60 mg/ℓ (as CaCO
3
),
calculated quarterly as a running annual average; and either the TTHM and HAA5
running annual averages are no greater than 0.040 mg/ℓ and 0.030 mg/ℓ,
respectively; or prior to the effective date for compliance in Section
611.380(b), the system has made a clear and irrevocable financial commitment,
not later than the effective date for compliance in Section 611.380(b), to use
technologies that will limit the levels of TTHMs and HAA5 to no more than 0.040
mg/ℓ and 0.030 mg/ℓ, respectively. A supplier must submit evidence
of a clear and irrevocable financial commitment, in addition to a schedule
containing milestones and periodic progress reports for installation and
operation of appropriate technologies, to the Agency for approval. Failure to
install and operate these technologies by the date in the approved schedule
will constitute a violation of an NPDWR.
D) The TTHM and HAA5 running annual averages are no greater than
0.040 mg/ℓ and 0.030 mg/ℓ, respectively, and the supplier uses only
chlorine for primary disinfection and maintenance of a residual in the
distribution system.
E) The supplier's source water SUVA, prior to any treatment and
measured monthly according to Section 611.381(d)(4), is less than or equal to
2.0 ℓ/mg-m, calculated quarterly as a running annual average.
F) The supplier's finished water SUVA, measured monthly according
to Section 611.381(d)(4), is less than or equal to 2.0 ℓ/mg-m, calculated
quarterly as a running annual average.
3) Additional Alternative Compliance Standards for Softening
Systems. A supplier practicing enhanced softening that cannot achieve the TOC
removals required by subsection (b)(2) may use the alternative compliance
standards in subsections (a)(3)(A) and (a)(3)(B) in lieu of complying with
subsection (b). A supplier must comply with monitoring requirements in Section
611.382(d). The alternative compliance standards are as follows:
A) The supplier may undertake softening that results in lowering
the treated water alkalinity to less than 60 mg/ℓ (as CaCO
3
),
measured monthly according to Section 611.381(d)(1) and calculated quarterly as
a running annual average; and
B) The supplier may undertake softening that results in removing
at least 10 mg/ℓ of magnesium hardness (as CaCO
3
), measured
monthly according to Section 611.381(d)(6) and calculated quarterly as a
running annual average.
b) Enhanced Coagulation and Enhanced Softening Performance
Requirements
1) A supplier must achieve the percent reduction of TOC specified
in subsection (b)(2) between the source water and the combined filter effluent,
unless the Agency approves a supplier's request for alternate minimum TOC
removal (Step 2) requirements under subsection (b)(3).
2) Required
Step 1 TOC reductions, indicated in the following table, are based upon
specified source water parameters measured in
compliance
with Section 611.381(d). A supplier practicing softening must meet the Step 1
TOC reductions in the far-right column (source water alkalinity greater than 120
mg/ℓ) for the following specified source water TOC:
Step
1 Required Removal of TOC by Enhanced Coagulation and Enhanced Softening for a
Subpart B System
Supplier
Using Conventional
Treatment
1,2
Source-water
TOC, mg/ℓ
Source-water alkalinity, mg/ℓ
as CaCO
3
0-60
> 60-120
> 120
3
> 2.0-4.0
35.0%
25.0%
15.0%
> 4.0-8.0
45.0%
35.0%
25.0%
> 8.0
50.0%
40.0%
30.0%
1
A supplier meeting at least one of the conditions in
subsections (a)(2)(A) through (a)(2)(F) are not required to operate with
enhanced coagulation.
2
A softening system that meets one of the alternative
compliance standards in subsection (a)(3) is not required to operate with
enhanced softening.
3
A supplier that practices softening must meet the TOC
removal requirements in this column.
3) A Subpart B conventional treatment system supplier that cannot
achieve the Step 1 TOC removals required by subsection (b)(2) due to water
quality parameters or operational constraints must apply to the Agency, within
three months after failure to achieve the TOC removals required by subsection
(b)(2), for approval of alternative minimum TOC (Step 2) removal requirements
submitted by the supplier. If the PWS cannot achieve the Step 1 TOC removal
requirement due to water quality parameters or operational constraints, the
Agency must approve the use of the Step 2 TOC removal requirement. If the
Agency approves the alternative minimum TOC removal (Step 2) requirements, the
Agency may make those requirements retroactive for the purposes of determining
compliance. Until the Agency approves the alternative minimum TOC removal
(Step 2) requirements, the supplier must meet the Step 1 TOC removals contained
in subsection (b)(2).
4) Alternative Minimum TOC Removal (Step 2) Requirements. An
application made to the Agency by an enhanced coagulation system supplier for
approval of alternative minimum TOC removal (Step 2) requirements under
subsection (b)(3) must include, at a minimum, results of bench- or pilot-scale
testing conducted under subsection (b)(4)(B). The submitted bench- or
pilot-scale testing must be used to determine the alternative enhanced
coagulation level.
A) For the purposes of this Subpart I, "alternative enhanced
coagulation level" is defined as coagulation at a coagulant dose and pH,
as determined by the method described in subsections (b)(4)(A) through (b)(4)(E),
such that an incremental addition of 10 mg/ℓ of alum (or equivalent
amount of ferric salt) results in a TOC removal of less than or equal to 0.3
mg/ℓ. The percent removal of TOC at this point on the "TOC removal
versus coagulant dose" curve is then defined as the minimum TOC removal
required for the supplier. Once approved by the Agency, this minimum
requirement supersedes the minimum TOC removal required by the table in
subsection (b)(2). This requirement will be effective until such time as the
Agency approves a new value based on the results of a new bench- and
pilot-scale test. Failure to achieve alternative minimum TOC removal levels is
a violation of National Primary Drinking Water Regulations.
B) Bench- or pilot-scale testing of enhanced coagulation must be
conducted by using representative water samples and adding 10 mg/ℓ
increments of alum (or equivalent amounts of ferric salt) until the pH is
reduced to a level less than or equal to the enhanced coagulation Step 2 target
pH shown in the following table:
Enhanced Coagulation Step 2 Target pH
Alkalinity (mg/ℓ as CaCO
3
)
Target pH
0-60
5.5
> 60-120
6.3
> 120-240
7.0
> 240
7.5
C) For waters with alkalinities of less than 60 mg/ℓ for
which addition of small amounts of alum or equivalent addition of iron
coagulant drives the pH below 5.5 before significant TOC removal occurs, the
supplier must add necessary chemicals to maintain the pH between 5.3 and 5.7 in
samples until the TOC removal of 0.3 mg/ℓ per 10 mg/ℓ alum added
(or equivalent addition of iron coagulant) is reached.
D) The supplier may operate at any coagulant dose or pH necessary
(consistent with other NPDWRs) to achieve the minimum TOC percent removal
approved under subsection (b)(3).
E) If the TOC removal is consistently less than 0.3 mg/ℓ of
TOC per 10 mg/ℓ of incremental alum dose at all dosages of alum (or
equivalent addition of iron coagulant), the water is deemed to contain TOC not
amenable to enhanced coagulation. The supplier may then apply to the Agency
for a waiver of enhanced coagulation requirements. If the TOC removal is
consistently less than 0.3 mg/ℓ of TOC per 10 mg/ℓ of incremental
alum dose at all dosages of alum (or equivalent addition of iron coagulant),
the Agency must grant the waiver of enhanced coagulation requirements.
c) Compliance Calculations
1) A Subpart B system supplier other than those identified in
subsection (a)(2) or (a)(3) must comply with requirements contained in
subsection (b)(2) or (b)(3). A supplier must calculate compliance quarterly,
beginning after the supplier has collected 12 months of data, by determining an
annual average using the following method:
A) Determine actual monthly TOC percent removal, equal to the
following:
B) Determine the required monthly TOC percent removal.
C) Divide the value in subsection (c)(1)(A) by the value in
subsection (c)(1)(B).
D) Add together the results of subsection (c)(1)(C) for the last
12 months and divide by 12.
E) If the value calculated in subsection (c)(1)(D) is less than
1.00, the supplier is not in compliance with the TOC percent removal
requirements.
2) A supplier may use the provisions in subsections (c)(2)(A)
through (c)(2)(E) in lieu of the calculations in subsection (c)(1)(A) through
(c)(1)(E) to determine compliance with TOC percent removal requirements.
A) In any month that the supplier's treated or source water TOC
level, measured according to Section 611.381(d)(3), is less than 2.0 mg/ℓ,
the supplier may assign a monthly value of 1.0 (in lieu of the value calculated
in subsection (c)(1)(C)) when calculating compliance under the provisions of
subsection (c)(1).
B) In any month that a system practicing softening removes at
least 10 mg/ℓ of magnesium hardness (as CaCO
3
), the supplier
may assign a monthly value of 1.0 (in lieu of the value calculated in subsection
(c)(1)(C)) when calculating compliance under the provisions of subsection
(c)(1).
C) In any month that the system's source water SUVA, prior to any
treatment and measured according to Section 611.381(d)(4), is less than or
equal to 2.0 ℓ/mg-m, the supplier may assign a monthly value of 1.0 (in
lieu of the value calculated in subsection (c)(1)(C)) when calculating
compliance under the provisions of subsection (c)(1).
D) In any month that the system's finished water SUVA, measured
according to Section 611.381(d)(4), is less than or equal to 2.0 ℓ/mg-m,
the supplier may assign a monthly value of 1.0 (in lieu of the value calculated
in subsection (c)(1)(C)) when calculating compliance under the provisions of
subsection (c)(1).
E) In any month that a system practicing enhanced softening lowers
alkalinity below 60 mg/ℓ (as CaCO
3
), the supplier may assign a
monthly value of 1.0 (in lieu of the value calculated in subsection (c)(1)(C))
when calculating compliance under the provisions of subsection (c)(1).
3) A Subpart B system supplier using conventional treatment may
also comply with the requirements of this Section by meeting the standards in
subsection (a)(2) or (a)(3).
d) Treatment Technique Requirements for Disinfection Byproduct
(DBP) Precursors. Treatment techniques to control the level of disinfection
byproduct (DBP) precursors in drinking water treatment and distribution
systems, for a Subpart B system supplier using conventional treatment, are
enhanced coagulation or enhanced softening.
BOARD NOTE:
Derived from 40 CFR 141.135.