35 Ill. Adm. Code 6110.611.533
Filtered PWSs
TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE F: PUBLIC WATER SUPPLIES
CHAPTER I: POLLUTION CONTROL BOARD
PART 611 PRIMARY DRINKING WATER STANDARDS
SECTION 611.533 FILTERED PWSS
Section 611.533 Filtered
PWSs
A supplier using a surface water
source or a groundwater source under the direct influence of surface water and providing
filtration treatment must monitor in compliance with this Section.
a) The supplier must perform turbidity measurements Section
611.250 requires on representative samples of the PWS's filtered water every
four hours (or more frequently) when the supplier serves water to the public.
A supplier may substitute continuous turbidity monitoring for grab sample
monitoring if it validates the continuous measurement for accuracy on a regular
basis using a protocol the Agency approved in a SEP. For a supplier using slow
sand filtration or filtration treatment other than conventional treatment,
direct filtration, or diatomaceous earth filtration, the Agency must reduce the
sampling frequency to once per day in a SEP if the Agency determines that less
frequent monitoring is sufficient to indicate effective filtration
performance. For a supplier serving 500 or fewer persons, the Agency must
reduce the turbidity sampling frequency to once per day in a SEP if the Agency
determines that less frequent monitoring is sufficient to indicate effective
filtration performance regardless of the type of filtration treatment used.
b) RDC Entering Distribution System
1) Suppliers Serving More Than 3300 Persons. The supplier must
continuously monitor the RDC of the water entering the distribution system, and
the supplier must record the lowest value each day, except that the supplier
may conduct grab sampling every four hours in lieu of continuous monitoring if
there is a failure in the continuous monitoring equipment, but not for more
than five working days following the equipment failure.
2) Suppliers Serving 3,300 or Fewer Persons. The supplier may
take grab samples in lieu of providing continuous monitoring on an ongoing
basis at the frequencies each day Table C prescribes. If at any time the RDC
falls below 0.2 mg/L in a system using grab sampling in lieu of continuous
monitoring, the supplier must take a grab sample every four hours until RDC is
equal to or greater than 0.2 mg/L.
c) Points of Measurement
1) The supplier must measure the RDC at least at the same points
in the distribution system and at the same time as sampling total coliforms, as
Sections 611.1054 through 611.1058 specify. The Agency must allow a supplier using
both a surface water source and a groundwater source or a groundwater source
under direct influence of surface water and a groundwater source to take RDC
samples at points other than the total coliform sampling points if the Agency
determines that those points are more representative of treated (disinfected)
water quality within the distribution system. The supplier may measure HPC, as
Section 611.531(a) specifies, in lieu of RDC.
2) Subsection (c)(1) does not apply if the Agency determines under
Section 611.213(c) that a system has no means for having a certified laboratory
analyze a sample for PHC under the requisite time and temperature conditions
Section 611.531(a) specifies and the supplier provides adequate disinfection in
its distribution system.
BOARD NOTE: This
Section derives from 40 CFR 141.74(c).