35 Ill. Adm. Code 6110.611.971
Routine Monitoring
TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE F: PUBLIC WATER SUPPLIES
CHAPTER I: POLLUTION CONTROL BOARD
PART 611 PRIMARY DRINKING WATER STANDARDS
SECTION 611.971 ROUTINE MONITORING
Section 611.971 Routine Monitoring
a) Monitoring
1) If a
supplier submitted an IDSE report, it must begin monitoring at the locations
and during the months that the supplier has recommended in its IDSE report
submitted under Section 611.925, following the schedule in Section 611.970(c),
unless the Agency, by a SEP, requires other locations or additional locations
after its review. If the supplier submitted a 40/30 certification under
Section 611.923, it qualified for a very small system waiver under Section
611.924, or it is a NTNCWS that serves fewer than 10,000 persons, the supplier
must monitor at the locations and on the dates identified in its monitoring
plan as described in Section 611.382(f), updated as required by Section
611.972.
2) The
supplier must monitor at no fewer than the number of locations identified in
the applicable of subsections (a)(2)(A) through (a)(2)(M), subject to the
limitations of subsections (a)(2)(N) and (a)(2)(O).
A) A
Subpart B system supplier that serves fewer than 500 persons must monitor
annually at two distribution system monitoring locations during each monitoring
period.
B) A
Subpart B system supplier that serves 500 to 3,300 persons must monitor
quarterly at two distribution system monitoring locations during each
monitoring period.
C) A
Subpart B system supplier that serves 3,301 to 9,999 persons must monitor
quarterly at two distribution system monitoring locations during each
monitoring period.
D) A
Subpart B system supplier that serves 10,000 to 49,999 persons must monitor
quarterly at four distribution system monitoring locations during each
monitoring period.
E) A
Subpart B system supplier that serves 50,000 to 249,999 persons must monitor
quarterly at eight distribution system monitoring locations during each
monitoring period.
F) A
Subpart B system supplier that serves 250,000 to 999,999 persons must monitor
quarterly at 12 distribution system monitoring locations during each monitoring
period.
G) A
Subpart B system supplier that serves 1,000,000 to 4,999,999 persons must
monitor quarterly at 16 distribution system monitoring locations during each
monitoring period.
H) A
Subpart B system supplier that serves 5,000,000 or more persons must monitor
quarterly at 20 distribution system monitoring locations during each monitoring
period.
I) A groundwater
system supplier that serves fewer than 500 persons must monitor annually at two
distribution system monitoring locations during each monitoring period.
J) A
groundwater system supplier that serves 500 to 9,999 persons must monitor
annually at two distribution system monitoring locations during each monitoring
period.
K) A
groundwater system supplier that serves 10,000 to 99,999 persons must monitor
quarterly at four distribution system monitoring locations during each
monitoring period.
L) A groundwater
system supplier that serves 100,000 to 499,999 persons must monitor quarterly
at six distribution system monitoring locations during each monitoring period.
M) A
groundwater system supplier that serves 500,000 or more persons must monitor
quarterly at eight distribution system monitoring locations during each
monitoring period.
N) The
supplier must monitor during month of highest DBP concentrations.
O) A
supplier on quarterly monitoring must take dual sample sets every 90 days at
each monitoring location, except for a Subpart B system supplier that serves
500 to 3,300. A groundwater system supplier that serves 500 to 9,999 persons that
is on annual monitoring must take dual sample sets at each monitoring
location. Any other supplier that is on annual monitoring or that is a Subpart
B system supplier that serves 500 to 3,300 is required to take individual TTHM
and HAA5 samples (instead of a dual sample set) at the locations with the
highest TTHM and HAA5 concentrations, respectively. For a supplier that serves
fewer than 500 people, only one location with a dual sample set per monitoring
period is needed if the highest TTHM and HAA5 concentrations occur at the same
location and month.
3) If a
supplier is an undisinfected system that begins using a disinfectant other than
UV light after the dates in Subpart W for complying with the IDSE requirements,
the supplier must consult with the Agency to identify compliance monitoring
locations for this Subpart Y. The supplier must then develop a monitoring plan
under Section 611.972 that includes those monitoring locations.
b) Analytical
Methods. A supplier must use an approved method listed in Section 611.381 for
TTHM and HAA5 analyses in this Subpart Y. Analyses must be conducted by laboratories
that have received certification as specified in Section 611.381.
BOARD NOTE: Derived from 40 CFR 141.621.