d)        Detection Limits. Specific detection limits apply for this
Subpart N (this list includes MCLs from Section 611.301 are for information
purposes only):
Contaminant
MCL (mg/L,
except asbestos)
Method
Detection Limit (mg/L)
Antimony
0.006
Atomic absorption −
furnace technique
0.003
Atomic absorption −
furnace technique (stabilized temperature)
0.0008
5
Inductively coupled plasma-mass
spectrometry
0.0004
Atomic absorption −
gaseous hydride technique
0.001
Arsenic
0.010
Atomic absorption −
furnace technique
0.001
Atomic absorption −
furnace technique (stabilized temperature)
0.00005
6
Atomic absorption − gaseous
hydride technique
0.001
Inductively coupled
plasma-mass spectrometry
0.0014
7
Asbestos
7 MFL
1
Transmission electron
microscopy
0.01
MFL
Barium
2
Atomic absorption −
furnace technique
0.002
Atomic absorption −
direct aspiration technique
0.1
Inductively coupled plasma arc
furnace
0.002
Inductively coupled plasma
0.001
Beryllium
0.004
Atomic absorption −
furnace technique
0.0002
Atomic absorption −
furnace technique (stabilized temperature)
0.00002
5
Inductively coupled plasma
2
0.0003
Inductively coupled
plasma-mass spectrometry
0.0003
Cadmium
0.005
Atomic absorption −
furnace technique
0.0001
Inductively coupled plasma
0.001
Chromium
0.1
Atomic absorption −
furnace technique
0.001
Inductively coupled plasma
0.007
Inductively coupled plasma
0.001
Cyanide
0.2
Distillation,
spectrophotometric
3
0.02
Automated distillation,
spectrophotometric
3
0.005
Distillation, selective
electrode
3
0.05
Distillation, amenable,
spectrophotometric
4
0.02
UV, distillation,
spectrophotometric
8
0.0005
Micro distillation, flow
injection, spectrophotometric
3
0.0006
Ligand exchange with
amperometry
4
0.0005
Mercury
0.002
Manual cold vapor technique
0.0002
Automated cold vapor technique
0.0002
Nickel
No MCL
Atomic absorption −
furnace technique
0.001
Atomic absorption −
furnace technique (stabilized temperature)
0.0006
5
Inductively coupled plasma
2
0.005
Inductively coupled
plasma-mass spectrometry
0.0005
Nitrate (as N)
10
Manual cadmium reduction
0.01
Automated hydrazine reduction
0.01
Automated cadmium reduction
0.05
Ion-selective electrode
1
Ion chromatography
0.01
Capillary ion
electrophoresis
0.076
Nitrite (as N)
1
Spectrophotometric
0.01
Automated cadmium reduction
0.05
Manual cadmium reduction
0.01
Ion chromatography
0.004
Capillary ion
electrophoresis
0.103
Selenium
0.05
Atomic absorption −
furnace technique
0.002
Atomic absorption −
gaseous hydride technique
0.002
Thallium
0.002
Atomic absorption −
furnace technique
0.001
Atomic absorption −
furnace technique (stabilized temperature)
0.0007
5
Inductively coupled
plasma-mass spectrometry
0.0003
Footnotes.
1
"MFL" means millions
of fibers per liter less than 10 μm.
2
Using a 2x preconcentration
step as noted in USEPA 200.7 (94). Lower MDLs are possible when using a 4x
preconcentration.
3
Screening method for total cyanides.
4
Measures "free"
cyanides when omitting distillation, digestion, or ligand exchange.
5
Lower MDLs are possible using
stabilized temperature graphite furnace atomic absorption.
6
The MDL for USEPA 200.9 (94) (atomic
absorption-platform furnace (stabilized temperature)) resulted using a 2x
concentration step during sample digestion. The MDL using direct analyses
(i.e., no sample digestion) is higher. Using multiple depositions, USEPA
200.9 (94) can obtain an MDL of 0.0001 mg/L.
7
Using selective ion
monitoring, USEPA 200.8 (94) (ICP-MS) is capable of obtaining an MDL of
0.0001 mg/L.
8
Measures total cyanides when using
UV-digestor and "free" cyanides when bypassing UV-digestor.
BOARD NOTE:Â Subsections (a)
through (c) derive from 40 CFR 141.23 preamble, and subsection (d) derives from
40 CFR 141.23 (a)(4)(i) and appendix A to subpart C of 40 CFR 141. See the
Board Note at Section 611.301(b) relating to the MCL for nickel.