35 Ill. Adm. Code 616.704
Design and Operating Requirements for Above-Ground Storage Tanks
Section 616
Section 616.704Â Design and
Operating Requirements for Above-Ground Storage Tanks
a)Â Â Â Â Â Â Â Â The owner or operator of a tank must not cause or allow:
1)Â Â Â Â Â Â Â Â Materials to be placed in a tank if such materials could cause
the tank to rupture, leak, corrode, or otherwise fail.
2)Â Â Â Â Â Â Â Â Uncovered tanks to be placed or operated so as to maintain
less than 60 centimeters (2 feet) of freeboard unless:
A)Â Â Â Â Â Â Â The tank is equipped with a containment structure (e.g., dike
or trench), a drainage control system, or a diversion structure (e.g., standby
tank); and
B)Â Â Â Â Â Â Â The containment structure, drainage control system, or
diversion structure has a capacity that equals or exceeds the volume of the top
60 centimeters (2 feet) of the tank.
3)Â Â Â Â Â Â Â Â Material to be continuously fed into a tank, unless the tank
is equipped with a means to stop this inflow (e.g., a feed cutoff system or a
bypass system to a standby tank).
4)Â Â Â Â Â Â Â Â Incompatible materials to be placed in the same tank.
5)Â Â Â Â Â Â Â Â Material to be placed in a tank that previously held an
incompatible material unless the incompatible material has been washed from the
tank.
6)Â Â Â Â Â Â Â Â Ignitable or reactive material to be placed in a tank unless:
A)Â Â Â Â Â Â Â The material is stored or treated in such a way that it is
protected from any material or conditions that may cause it to ignite or react;
or
B)Â Â Â Â Â Â Â The tank is used solely for emergencies.
b)Â Â Â Â Â Â Â Â The owner or operator must provide and maintain primary containment
for the tank such that:
1)Â Â Â Â Â Â Â Â The tank has a minimum shell thickness that ensures that the
tank will not fail (e.g., collapse, rupture).
2)Â Â Â Â Â Â Â Â The tank is compatible with the material to be placed in the
tank or the tank is lined with a substance that is compatible with the material
to be placed in the tank.
c)Â Â Â Â Â Â Â Â The owner or operator must provide and maintain secondary
containment for the tank that:
1)Â Â Â Â Â Â Â Â Is capable of containing the volume of the largest tank or 10%
of the total volume for all tanks, whichever is greater;
2)Â Â Â Â Â Â Â Â Is constructed of material capable of containing a spill until
cleanup occurs (e.g., concrete or clay). The base of the secondary containment
area must be capable of minimizing vertical migration of a spill until cleanup
occurs (e.g., concrete or clay);
3)Â Â Â Â Â Â Â Â Has cover (e.g., crushed rock or vegetative growth) on earthen
embankments sufficient to prevent erosion; and
4)Â Â Â Â Â Â Â Â Isolates the tank from storm water drains and from combined
storm water drains and sanitary sewer drains.
d)Â Â Â Â Â Â Â Â If incompatible materials are handled at the site, secondary
containment sufficient to isolate the units containing the incompatible
materials must be provided.
e)Â Â Â Â Â Â Â Â The owner or operator of a tank must also:
1)Â Â Â Â Â Â Â Â Test above-ground tanks and associated piping every five years
for structural integrity.
2)Â Â Â Â Â Â Â Â Remove uncontaminated storm water runoff from the secondary
containment area immediately after a precipitation event.
3)Â Â Â Â Â Â Â Â Handle contaminated storm water runoff in compliance with 35
Ill. Adm. Code 302.Subpart A.
4)Â Â Â Â Â Â Â Â Provide a method for obtaining a sample from each tank.
5)Â Â Â Â Â Â Â Â Install, maintain, and operate a material level indicator on
each tank.
6)Â Â Â Â Â Â Â Â When not in use, lock all gauges and valves that are used to
inspect levels in the tank. All such devices must be located within the
containment structure.