35 Ill. Adm. Code 724.445
Operating Requirements
Section 724
Section 724.445 Operating
Requirements
a) An incinerator must be operated in accordance with operating
requirements specified in the permit. These will be specified on a
case-by-case basis as those demonstrated (in a trial burn or in alternative
data as specified in Section 724.444(b) and included with Part B of the
facility's permit application) to be sufficient to comply with the performance
standards of Section 724.443.
b) Each set of operating requirements will specify the
composition of the waste feed (including acceptable variations in the physical
or chemical properties of the waste feed that will not affect compliance with
the performance requirement of Section 724.443) to which the operating
requirements apply. For each such waste feed, the permit will specify
acceptable operating limits, including the following conditions:
1) Carbon monoxide (CO) level in the stack exhaust gas;
2) Waste feed rate;
3) Combustion temperature;
4) An appropriate indicator of combustion gas velocity;
5) Allowable variations in incinerator system design or operating
procedures; and
6) Such other operating requirements as are necessary to ensure
that the performance standards of Section 724.443 are met.
c) During start-up and shut-down of an incinerator, hazardous
waste (except wastes exempted in accordance with Section 724.440) must not be
fed into the incinerator unless the incinerator is operating within the
conditions of operation (temperature, air feed rate, etc.) specified in the
permit.
d) Fugitive emissions from the combustion zone must be controlled
by the following:
1) Keeping the combustion zone totally sealed against fugitive
emissions;
2) Maintaining a combustion zone pressure lower than atmospheric
pressure; or
3) An alternative means of control demonstrated (with Part B of
the permit application) to provide fugitive emissions control equivalent to
maintenance of combustion zone pressure lower than atmospheric pressure.
e) An incinerator must be operated with a functioning system to
automatically cut off waste feed to the incinerator when operating conditions
deviate from limits established under subsection (a).
f) An incinerator must cease operation when changes in waste
feed, incinerator design, or operating conditions exceed limits designated in
its permit.