35 Ill. Adm. Code 725.1101
Design and Operating Standards
Section 725
Section 725.1101Â Design and Operating
Standards
a)Â Â Â Â Â Â Â Â All containment buildings must comply with the following
design and operating standards:
1)Â Â Â Â Â Â Â Â The containment building must be completely enclosed with a
floor, walls, and a roof to prevent exposure to the elements (e.g.,
precipitation, wind, run on) and to assure containment of managed wastes;
2)Â Â Â Â Â Â Â Â The floor and containment walls of the unit, including the
secondary containment system if required under subsection (b), must be designed
and constructed of materials of sufficient strength and thickness to support
themselves, the waste contents, and any personnel and heavy equipment that
operate within the unit, and to prevent failure due to pressure gradients,
settlement, compression, or uplift, physical contact with the hazardous wastes
to which they are exposed; climatic conditions; and the stresses of daily
operation, including the movement of heavy equipment within the unit and
contact of such equipment with containment walls. The unit must be designed so
that it has sufficient structural strength to prevent collapse or other
failure. All surfaces to be in contact with hazardous wastes must be
chemically compatible with those wastes. The containment building must meet
the structural integrity requirements established by professional organizations
generally recognized by the industry such as the American Concrete Institute (ACI)
and the American Society of Testing Materials (ASTM). If appropriate to the
nature of the waste management operation to take place in the unit, an
exception to the structural strength requirement may be made for light-weight
doors and windows that meet the following criteria:
A)Â Â Â Â Â Â Â They provide an effective barrier against fugitive dust
emissions under subsection (c)(1)(D); and
B)Â Â Â Â Â Â Â The unit is designed and operated in a fashion that assures
that wastes will not actually come in contact with these openings;
3)Â Â Â Â Â Â Â Â Incompatible hazardous wastes or treatment reagents must not
be placed in the unit or its secondary containment system if they could cause
the unit or secondary containment system to leak, corrode, or otherwise fail;
and
4)Â Â Â Â Â Â Â Â A containment building must have a primary barrier designed to
withstand the movement of personnel, waste, and handling equipment in the unit
during the operating life of the unit and appropriate for the physical and
chemical characteristics of the waste to be managed.
b)Â Â Â Â Â Â Â Â For a containment building used to manage hazardous wastes
containing free liquids or treated with free liquids (the presence of which is
determined by the paint filter test, a visual examination, or other appropriate
means), the owner or operator must include the following design features:
1)Â Â Â Â Â Â Â Â A primary barrier designed and constructed of materials to
prevent the migration of hazardous constituents into the barrier (e.g., a
geomembrane covered by a concrete wear surface).
2)Â Â Â Â Â Â Â Â A liquid collection and removal system to minimize the
accumulation of liquid on the primary barrier of the containment building as
follows:
A)Â Â Â Â Â Â Â The primary barrier must be sloped to drain liquids to the
associated collection system; and
B)Â Â Â Â Â Â Â Liquids and waste must be collected and removed to minimize
hydraulic head on the containment system at the earliest practicable time.
3)Â Â Â Â Â Â Â Â A secondary containment system including a secondary barrier
designed and constructed to prevent migration of hazardous constituents into
the barrier, and a leak detection system that is capable of detecting failure
of the primary barrier and collecting accumulated hazardous wastes and liquids
at the earliest practicable time.
A)Â Â Â Â Â Â Â The requirements of the leak detection component of the
secondary containment system are satisfied by installation of a system that is,
at a minimum, as follows:
i)Â Â Â Â Â Â Â Â Â It is constructed with a bottom slope of 1 percent or more;
and
ii)Â Â Â Â Â Â Â Â It is constructed of a granular drainage material with a
hydraulic conductivity of 1 x 10
-2
cm/sec or more and a thickness of
12 inches (30.5 cm) or more, or constructed of synthetic or geonet drainage
materials with a transmissivity of 3 x 10
-5
m
2
/sec or
more.
B)Â Â Â Â Â Â Â If treatment is to be conducted in the building, an area in
which such treatment will be conducted must be designed to prevent the release
of liquids, wet materials, or liquid aerosols to other portions of the
building.
C)Â Â Â Â Â Â Â The secondary containment system must be constructed of
materials that are chemically resistant to the waste and liquids managed in the
containment building and of sufficient strength and thickness to prevent
collapse under the pressure exerted by overlaying materials and by any equipment
used in the containment building. (Containment buildings can serve as
secondary containment systems for tanks placed within the building under
certain conditions. A containment building can serve as an external liner
system for a tank, provided it meets the requirements of Section 725.293(e)(1).Â
In addition, the containment building must meet the requirements of Section
725.293(b) and (c) to be an acceptable secondary containment system for a
tank.)
c)Â Â Â Â Â Â Â Â An owner or operator of a containment building must do each of
the following:
1)Â Â Â Â Â Â Â Â It must use controls and practice to ensure containment of the
hazardous waste within the unit, and at a minimum do each of the following:
A)Â Â Â Â Â Â Â It must maintain the primary barrier to be free of significant
cracks, gaps, corrosion, or other deterioration that could cause hazardous
waste to be released from the primary barrier;
B)Â Â Â Â Â Â Â It must maintain the level of the stored or treated hazardous
waste within the containment walls of the unit so that the height of any
containment wall is not exceeded;
C)Â Â Â Â Â Â Â It must take measures to prevent the tracking of hazardous
waste out of the unit by personnel or by equipment used in handling the waste.Â
An area must be designated to decontaminate equipment and any rinsate must be
collected and properly managed; and
D)Â Â Â Â Â Â Â It must take measures to control fugitive dust emissions such
that any openings (doors, windows, vents, cracks, etc.) exhibit no visible
emissions (see Reference Method 22 (Visual Determination of Fugitive Emissions
from Material Sources and Smoke Emissions from Flares) in appendix A to 40 CFR
60 (Test Methods), incorporated by reference in 35 Ill. Adm. Code 720.111(b)).Â
In addition, all associated particulate collection devices (e.g., fabric
filter, electrostatic precipitator, etc.) must be operated and maintained with
sound air pollution control practices (see 40 CFR 60 for guidance). This state
of no visible emissions must be maintained effectively at all times during
routine operating and maintenance conditions, including when vehicles and
personnel are entering and exiting the unit;
BOARD NOTE:Â At 40 CFR 264.1101(c)(1)(iv),
USEPA cites "40 CFR part 60, subpart 292". At 57 Fed. Reg. 37217 (Aug.
18, 1992), USEPA repeats this citation in the preamble discussion of adoption
of the rules. No such provision exists in the Code of Federal Regulations. While
40 CFR 60.292 of the federal regulations pertains to control of fugitive dust
emissions, that provision is limited in its application to glass melting
furnaces. Â The Board has chosen to use the general citation:Â "40 CFR 60".
2)Â Â Â Â Â Â Â Â It must obtain and keep on site a certification by a qualified
Professional Engineer that the containment building design meets the
requirements of subsections (a) through (c);
3)Â Â Â Â Â Â Â Â Throughout the active life of the containment building, if the
owner or operator detects a condition that could lead to or has caused a
release of hazardous waste, it must repair the condition promptly, in
accordance with the following procedures:
A)Â Â Â Â Â Â Â Upon detection of a condition that has lead to a release of
hazardous wastes (e.g., upon detection of leakage from the primary barrier) the
owner or operator must do the following:
i)Â Â Â Â Â Â Â Â Â Enter a record of the discovery in the facility operating
record;
ii)Â Â Â Â Â Â Â Â Immediately remove the portion of the containment building
affected by the condition from service;
iii)Â Â Â Â Â Â Â Determine what steps must be taken to repair the containment
building, remove any leakage from the secondary collection system, and
establish a schedule for accomplishing the cleanup and repairs; and
iv)Â Â Â Â Â Â Â Within seven days after the discovery of the condition, notify
the Agency in writing of the condition, and within 14 working days, provide a
written notice to the Agency with a description of the steps taken to repair
the containment building, and the schedule for accomplishing the work;
B)Â Â Â Â Â Â Â The Agency must review the information submitted, make a
determination in accordance with Section 34 of the Act, regarding whether the
containment building must be removed from service completely or partially until
repairs and cleanup are complete, and notify the owner or operator of the
determination and the underlying rationale in writing; and
C)Â Â Â Â Â Â Â Upon completing all repairs and cleanup the owner and operator
must notify the Agency in writing and provide a verification, signed by a
qualified, registered professional engineer, that the repairs and cleanup have
been completed according to the written plan submitted in accordance with
subsection (c)(3)(A)(iv); and
4)Â Â Â Â Â Â Â Â At least once every seven days, the owner or operator must
inspect and record in the facility's operating record data gathered from
monitoring and leak detection equipment, as well as the containment building
and the area immediately surrounding the containment building, to detect signs
of releases of hazardous waste.
d)Â Â Â Â Â Â Â Â For a containment building that contains areas both with and
without secondary containment, the owner or operator must do the following:
1)Â Â Â Â Â Â Â Â Design and operate each area in accordance with the
requirements enumerated in subsections (a) through (c);
2)Â Â Â Â Â Â Â Â Take measures to prevent the release of liquids or wet
materials into areas without secondary containment; and
3)Â Â Â Â Â Â Â Â Maintain in the facility's operating log a written description
of the operating procedures used to maintain the integrity of areas without
secondary containment.
e)Â Â Â Â Â Â Â Â Notwithstanding any other provision of this Subpart DD, the
Agency must, in writing, allow the use of alternatives to the requirements for
secondary containment for a permitted containment building where the Agency has
determined that the facility owner or operator has adequately demonstrated that
the only free liquids in the unit are limited amounts of dust suppression
liquids required to meet occupational health and safety requirements, and where
containment of managed wastes and liquids can be assured without a secondary
containment system.