35 Ill. Adm. Code 725.447
Monitoring and Inspections
Section 725
Section 725.447Â Monitoring
and Inspections
The owner or operator must
conduct, as a minimum, the following monitoring and inspections when
incinerating hazardous waste:
a)Â Â Â Â Â Â Â Â Existing instruments that relate to combustion and emission
control must be monitored at least every 15 minutes. Appropriate corrections
to maintain steady state combustion conditions must be made immediately either
automatically or by the operator. Instruments that relate to combustion and
emission control would normally include those measuring waste feed, auxiliary
fuel feed, air flow, incinerator temperature, scrubber flow, scrubber pH, and
relevant level controls.
b)Â Â Â Â Â Â Â Â The complete incinerator and associated equipment (pumps,
valves, conveyors, pipes, etc.) must be inspected at least daily for leaks,
spills, and fugitive emissions and all emergency shutdown controls and system
alarms must be checked to assure proper operation.