35 Ill. Adm. Code 726.210
Waiver of DRE Trial Burn for Boilers
Section 726
Section 726.210Â Waiver of
DRE Trial Burn for Boilers
Boilers that operate under the
special requirements of this Section, and that do not burn hazardous waste
containing (or derived from) USEPA hazardous waste numbers F020, F021, F022,
F023, F026, or F027, are considered to be in conformance with the DRE standard
of Section 726.204(a), and a trial burn to demonstrate DRE is waived. When
burning hazardous waste:
a)Â Â Â Â Â Â Â Â A minimum of 50 percent of fuel fired to the devices must be
fossil fuel, fuels derived from fossil fuel, tall oil, or, if approved by the
Agency on a case-by-case basis, other nonhazardous fuel with combustion
characteristics comparable to fossil fuel. Such fuels are termed "primary
fuel" for purposes of this Section. (Tall oil is a fuel derived from
vegetable and rosin fatty acids.)Â The 50 percent primary fuel firing rate must
be determined on a total heat or mass input basis, whichever results in the
greater mass feed rate of primary fuel fired;
b)        Boiler load must not be less than 40 percent. Boiler load is
the ratio at any time of the total heat input to the maximum design heat input;
c)Â Â Â Â Â Â Â Â Primary fuels and hazardous waste fuels must have a minimum
as-fired heating value of 8,000 Btu/lb, and each material fired in a burner
where hazardous waste is fired must have a heating value of at least 8,000
Btu/lb, as fired;
d)Â Â Â Â Â Â Â Â The device must operate in conformance with the CO standard
provided by Section 726.204(b)(1). Boilers subject to the waiver of the DRE
trial burn provided by this Section are not eligible for the alternative CO
standard provided by Section 726.204(c);
e)Â Â Â Â Â Â Â Â The boiler must be a water tube type boiler that does not feed
fuel using a stoker or stoker type mechanism; and
f)Â Â Â Â Â Â Â Â The hazardous waste must be fired directly into the primary
fuel flame zone of the combustion chamber with an air or steam atomization
firing system, mechanical atomization system or a rotary cup atomization system
under the following conditions:
1)        Viscosity. The viscosity of the hazardous waste fuel as fired
must not exceed 300 SSU;
2)        Particle size. When a high pressure air or steam atomizer,
low pressure atomizer or mechanical atomizer is used, 70 percent of the
hazardous waste fuel must pass through a 200 mesh (74 micron) screen, and when
a rotary cup atomizer is used, 70 percent of the hazardous waste must pass
through a 100 mesh (150 micron) screen;
3)        Mechanical atomization systems. Fuel pressure within a
mechanical atomization system and fuel flow rate must be maintained within the
design range taking into account the viscosity and volatility of the fuel;
4)        Rotary cup atomization systems. Fuel flow rate through a
rotary cup atomization system must be maintained within the design range taking
into account the viscosity and volatility of the fuel.