35 Ill. Adm. Code 727.900
Containment Buildings
Section 727.900Â Containment Buildings
a)Â Â Â Â Â Â Â Â Applicability
of This Section. This Section applies to the owner or operator of a facility
that treats or stores hazardous waste in containment buildings under a RCRA
standardized permit pursuant to 35 Ill. Adm. Code 703.Subpart J, except as
provided in Section 727.100(a)(2). Storage or treatment in a containment
building is not land disposal, as defined in 35 Ill. Adm. Code 728.102, if the
unit meets the requirements of subsections (b), (c), and (d).
BOARD NOTE:Â Subsection (a) is
derived from 40 CFR 267.1100.
b)Â Â Â Â Â Â Â Â Design
and Operating Standards for Containment Buildings. A containment building must
comply with the design and operating standards in this subsection (b). The
Agency may consider standards established by professional organizations
generally recognized by the industry, such as the American Concrete Institute
(ACI) or the American Society of Testing Materials (ASTM), in judging the
structural integrity requirements of this subsection (b).
1)Â Â Â Â Â Â Â Â The
containment building must be completely enclosed with a floor, walls, and a roof
to prevent exposure to the elements (e.g., precipitation, wind, run-on, etc.),
and to assure containment of managed wastes.
2)Â Â Â Â Â Â Â Â The
floor and containment walls of the unit, including the secondary containment
system, if required pursuant to subsection (d), must be designed and
constructed of manmade materials of sufficient strength and thickness to
accomplish the following:
A)Â Â Â Â Â Â Â They
must support themselves, the waste contents, and any personnel and heavy
equipment that operates within the unit;
B)Â Â Â Â Â Â Â They must
prevent failure due to any of the following causes:
i)Â Â Â Â Â Â Â Â Â Pressure
gradients, settlement, compression, or uplift;
ii)Â Â Â Â Â Â Â Â Physical
contact with the hazardous wastes to which they are exposed;
iii)Â Â Â Â Â Â Â Climatic
conditions;
iv)Â Â Â Â Â Â Â Stresses
of daily operation, including the movement of heavy equipment within the unit
and contact of such equipment with containment walls; or
v)Â Â Â Â Â Â Â Â Collapse
or other failure.
3)Â Â Â Â Â Â Â Â All
surfaces to be in contact with hazardous wastes must be chemically compatible
with those wastes.
4)Â Â Â Â Â Â Â Â The
facility owner or operator must not place incompatible hazardous wastes or
treatment reagents in the unit or its secondary containment system if they
could cause the unit or secondary containment system to leak, corrode, or
otherwise fail.
5)Â Â Â Â Â Â Â Â A
containment building must have a primary barrier designed to withstand the
movement of personnel, waste, and handling equipment in the unit during the
operating life of the unit and appropriate for the physical and chemical
characteristics of the waste to be managed.
6)Â Â Â Â Â Â Â Â If
appropriate to the nature of the waste management operation to take place in
the unit, an exception to the structural strength requirement may be made for
light-weight doors and windows that meet these criteria:
A)Â Â Â Â Â Â Â The
doors and windows provide an effective barrier against fugitive dust emissions
pursuant to subsection (c)(4); and
B)Â Â Â Â Â Â Â The
unit is designed and operated in a fashion that assures that wastes will not
actually come in contact with these openings.
7)Â Â Â Â Â Â Â Â The
facility owner or operator must inspect and record in the facility's operating
record, at least once every seven days, data gathered from monitoring equipment
and leak detection equipment, as well as the containment building and the area
immediately surrounding the containment building to detect signs of releases of
hazardous waste.
8)Â Â Â Â Â Â Â Â The
facility owner or operator must obtain certification by a qualified registered
professional engineer that the containment building design meets the
requirements of subsections (b)(1) through (b)(6), (c), and (d).
BOARD NOTE:Â Subsection (b) is
derived from 40 CFR 267.1101.
c)Â Â Â Â Â Â Â Â Other
Requirements for Preventing Releases. The facility owner or operator must use
controls and practices to ensure containment of the hazardous waste within the
unit and must meet the following minimum requirements:
1)Â Â Â Â Â Â Â Â It
must maintain the primary barrier to be free of significant cracks, gaps,
corrosion, or other deterioration that could cause hazardous waste to be
released from the primary barrier;
2)Â Â Â Â Â Â Â Â It
must maintain the level of the stored or treated hazardous waste within the
containment walls of the unit so that the height of any containment wall is not
exceeded;
3)Â Â Â Â Â Â Â Â It
must take measures to prevent personnel or by equipment used in handling the waste
from tracking hazardous waste out of the unit. The owner or operator must
designate an area to decontaminate equipment, and it must collect and properly
manage any rinsate; and
4)Â Â Â Â Â Â Â Â It
must take measures to control fugitive dust emissions such that any openings
(doors, windows, vents, cracks, etc.) exhibit no visible emissions (see Method
22 of appendix A to 40 CFR 60 (Visual Determination of Fugitive Emissions from
Material Sources and Smoke Emissions from Flares), incorporated by reference in
35 Ill. Adm. Code 720.111(b)). In addition, the owner or operator must operate
and maintain all associated particulate collection devices (for example, fabric
filter, electrostatic precipitator, etc.) with sound air pollution control
practices. The owner or operator must effectively maintain this state of no
visible emissions at all times during routine operating and maintenance
conditions, including when vehicles and personnel are entering and exiting the
unit.
BOARD NOTE:Â Subsection (c) is
derived from 40 CFR 267.1102.
d)Â Â Â Â Â Â Â Â Additional
Design and Operating Standards When Liquids Are in the Containment Building. If
a containment building will be used to manage hazardous wastes containing free
liquids or treated with free liquids, as determined by the paint filter test,
by a visual examination, or by other appropriate means, the facility owner or
operator must include the following:
1)Â Â Â Â Â Â Â Â A
primary barrier designed and constructed of materials to prevent the migration
of hazardous constituents into the barrier (for example, a geomembrane covered
by a concrete wear surface);
2)Â Â Â Â Â Â Â Â A
liquid collection and removal system to minimize the accumulation of liquid on
the primary barrier of the containment building, as follows:
A)Â Â Â Â Â Â Â The
primary barrier must be sloped to drain liquids to the associated collection
system; and
B)Â Â Â Â Â Â Â The
facility owner or operator must collect and remove liquids and waste to
minimize hydraulic head on the containment system at the earliest practicable
time;
3)Â Â Â Â Â Â Â Â A
secondary containment system, including a secondary barrier designed and
constructed to prevent migration of hazardous constituents into the barrier,
and a leak detection system capable of detecting failure of the primary barrier
and collecting accumulated hazardous wastes and liquids at the earliest
practical time, as follows:
A)Â Â Â Â Â Â Â The
facility owner or operator may meet the requirements of the leak detection
component of the secondary containment system by installing a system that meets
the following minimum construction requirements:
i)Â Â Â Â Â Â Â Â Â It
is constructed with a bottom slope of one percent or more; and
ii)Â Â Â Â Â Â Â Â It
is constructed of a granular drainage material with a hydraulic conductivity of
1 × 10
-2
cm/sec or more and a thickness of 12 inches (30.5 cm) or
more, or constructed of synthetic or geonet drainage materials with a
transmissivity of 3 × 10
-
5
m
2
sec or more;
B)Â Â Â Â Â Â Â If the
facility owner or operator will be conducting treatment in the building, it
must design the area in which the treatment will be conducted to prevent the
release of liquids, wet materials, or liquid aerosols to other portions of the
building; and
C)Â Â Â Â Â Â Â The
facility owner or operator must construct the secondary containment system
using materials that are chemically resistant to the waste and liquids managed
in the containment building and of sufficient strength and thickness to prevent
collapse under the pressure exerted by overlaying materials and by any
equipment used in the containment building.
BOARD NOTE:Â Subsection (d) is
derived from 40 CFR 267.1103.
e)Â Â Â Â Â Â Â Â Alternatives
to Secondary Containment Requirements. Notwithstanding any other provision of
this Section, the Agency must, in writing, allow the use of alternatives to the
requirements for secondary containment for a permitted containment building
where the Agency has determined that the facility owner or operator has
adequately demonstrated both of the following:
1)Â Â Â Â Â Â Â Â The
only free liquids in the unit are limited amounts of dust suppression liquids
required to meet occupational health and safety requirements; and
2)Â Â Â Â Â Â Â Â The
containment of managed wastes and dust suppression liquids can be assured
without a secondary containment system.
BOARD NOTE:Â Subsection (e) is
derived from 40 CFR 267.1104.
f)Â Â Â Â Â Â Â Â Requirements
Where the Containment Building Contains Areas Both With and Without Secondary
Containment. For a containment building that contains both areas that have
secondary containment and areas that do not have secondary containment, the
facility owner or operator must fulfill the following requirements:
1)Â Â Â Â Â Â Â Â It
must design and operate each area in accordance with the requirements
enumerated in subsections (b) through (d);
2)Â Â Â Â Â Â Â Â It
must take measures to prevent the release of liquids or wet materials into
areas without secondary containment; and
3)Â Â Â Â Â Â Â Â It
must maintain in the facility's operating log a written description of the
operating procedures used to maintain the integrity of areas without secondary
containment.
BOARD NOTE:Â Subsection (f) is
derived from 40 CFR 267.1105.
g)Â Â Â Â Â Â Â Â Requirements
in the Event of a Release. Throughout the active life of the containment
building, if the facility owner or operator detects a condition that could lead
to or has caused a release of hazardous waste, it must repair the condition
promptly, in accordance with the following procedures.
1)Â Â Â Â Â Â Â Â Upon
detection of a condition that has led to a release of hazardous waste (for
example, upon detection of leakage from the primary barrier), the owner or
operator must undertake each of the following actions:
A)Â Â Â Â Â Â Â It
must enter a record of the discovery in the facility operating record;
B)Â Â Â Â Â Â Â It
must immediately remove the portion of the containment building affected by the
condition from service;
C)Â Â Â Â Â Â Â It
must determine what steps it will need to take to repair the containment
building, to remove any leakage from the secondary collection system, and to
establish a schedule for accomplishing the cleanup and repairs; and
D)Â Â Â Â Â Â Â Within
seven days after the discovery of the condition, it must notify the Agency of
the condition, and within 14 working days, provide a written notice to the
Agency with a description of the steps taken to repair the containment
building, and the schedule for accomplishing the work.
2)Â Â Â Â Â Â Â Â The
Agency must review the information submitted, determine whether the containment
building must be removed from service completely or partially until repairs and
cleanup are complete, and notify the owner or operator of the determination and
the underlying rationale in writing.
3)Â Â Â Â Â Â Â Â Upon
completing all repairs and cleanup, the facility owner or operator must notify
the Agency in writing and provide a verification, signed by a qualified,
registered professional engineer, that the repairs and cleanup have been
completed according to the written plan submitted in accordance with subsection
(g)(1)(D).
BOARD NOTE:Â Subsection (g) is
derived from 40 CFR 267.1106.
h)Â Â Â Â Â Â Â Â A Containment
Building That Can Be Considered Secondary Containment. A containment building
can serve as an acceptable secondary containment system for tanks placed within
the building if both of the following conditions are fulfilled:
1)Â Â Â Â Â Â Â Â The
containment building can serve as an external liner system for a tank if it
meets the requirements of Section 727.290(g)(2); and
2)Â Â Â Â Â Â Â Â The
containment building also meets the requirements of Section 727.290(f)(1),
(f)(2)(A), and (f)(2)(B).
BOARD NOTE:Â Subsection (h) is
derived from 40 CFR 267.1107.
i)Â Â Â Â Â Â Â Â Â Requirements
When the Owner or Operator Stops Operating the Containment Building. When the
facility owner or operator close a containment building, it must remove or
decontaminate all waste residues, contaminated containment system components
(liners, etc.), contaminated subsoils, and structures and equipment
contaminated with waste and leachate and manage them as hazardous waste unless
35 Ill. Adm. Code 721.103(d) applies. The closure plan, closure activities,
cost estimates for closure, and financial responsibility for containment
buildings must meet all of the requirements specified in Sections 727.210 and
727.240.
BOARD NOTE:Â Subsection (i) is
derived from 40 CFR 267.1108.