35 Ill. Adm. Code 731.110
Applicability
Section 731
Section 731.110
Applicability
a) This
Part applies to all owners and operators of an Underground Storage Tank (UST)
system as defined in Section 731.112, except as otherwise provided in subsection
(b) or (c).
1) Previously
Deferred UST Systems. Airport hydrant fuel distribution systems, UST systems
with field-constructed tanks, and UST systems that store fuel solely for use by
emergency power generators must meet the requirements of this Part as follows:
A) Airport
hydrant fuel distribution systems and UST systems with field-constructed tanks
must meet the requirements in Subpart K of this Part.
B) This
subsection (a)(1)(B) corresponds with 40 CFR 280.11(a)(1)(ii), which subjects
UST systems that store fuel solely for use by emergency power generators
installed on or before October 13, 2015 to release detection requirements that
are outside the scope of the Board's regulations. This statement maintains
structural consistency with the federal regulations.
C) UST
systems that store fuel solely for use by emergency power generators installed
after October 13, 2015 must meet all applicable requirements of this Part at
the time of installation.
2) This
subsection (a)(2) subjects various partially excluded UST systems to specified
installation requirements outside the scope of the Board regulations. This
statement maintains structural consistency with the federal regulations.
b) Exclusions. The following UST systems are excluded from the
requirements of this Part:
1) Any UST system holding hazardous waste or a mixture of such
hazardous waste and other regulated substances.
2) Any wastewater treatment tank system that is part of a
wastewater treatment facility regulated under Section 12(f) of the Act [415
ILCS 5/12(f)].
3) Equipment or machinery that contains regulated substances for
operational purposes such as hydraulic lift tanks and electrical equipment
tanks.
4) Any UST system whose capacity is 110 gallons or less.
5) Any UST system that contains a de minimis concentration of
regulated substances.
6) Any emergency spill or overflow containment UST system that is
expeditiously emptied after used.
c) Partial Exclusions
1) Section
731.122 and Subpart K do not apply to any of the following:
A) Wastewater
treatment tank systems not covered under subsection (b)(2);
B) Aboveground
storage tanks associated with either of the following:
i) Airport
hydrant fuel distribution systems regulated under Subpart K; and
ii) UST
systems with field-constructed tanks regulated under Subpart K;
C) Any UST systems containing radioactive materials that are
regulated by the Nuclear Regulatory Commission under the Atomic Energy Act of
1954 (42 USC 2011 et seq.); and
D) Any UST system that is part of an emergency generator system at
nuclear power generation facilities licensed by the Nuclear Regulatory
Commission and subject to Nuclear Regulatory Commission requirements regarding
design and quality criteria, including but not limited to 10 CFR 50.
2) Owners
and operators subject to Title XVI of the Act are required to respond to
releases in accordance with 35 Ill. Adm. Code 734 instead of Subpart F of this
Part.
d) Heating Oil USTs
1) Definitions. The following definitions apply to this subsection
(d) only:
"Beneath
the surface of the ground" is as defined in Section 731.112.
"Consumptive use" with
respect to heating oil means consumed on the premises.
"Heating Oil" means
petroleum that is No. 1, No. 2, No. 4-light, No. 4-heavy, No. 5-light, No. 5-heavy,
or No. 6 technical grades of fuel oil; and other residual fuel oils including
navy special fuel oil and bunker C.
(Section 57.2 of the Act [415 ILCS
5/57.2])
"Heating Oil Underground
Storage Tank" or "Heating Oil UST" means an underground storage
tank used exclusively to store heating oil for consumptive use on the premises
where stored and which serves other than a farm or residential unit.
(Section
57.2 of the Act [415 ILCS 5/57.2])
"On the premises where
stored" with respect to heating oil means UST systems located on the same
property where the stored heating oil is used.
"Pipe" or
"piping" is as defined in Section 731.112.
"Regulated substance" is
as defined in Section 731.112.
"Tank" is as defined in
Section 731.112.
"Underground storage
tank" or "UST" means any one or combination of tanks (including
underground pipes connected thereto) that is used to contain an accumulation of
regulated substances, and the volume of which (including the volume of the
underground pipes connected thereto) is 10 per centum or more beneath the
surface of the ground.
2) Subsections (a) through (c) notwithstanding,
this Part
applies to owners and operators of any heating oil UST.
(Section 22.4(d)(4)
of the Act [415 ILCS 5/22.4(d)(4)])
3) The owner or operator of a heating oil UST must comply with
the same requirements as the owner or operator of a petroleum UST, as defined
in Section 731.112, any other provisions of this Part notwithstanding.
BOARD NOTE: This subsection (d) implements Section 22.4(d)(4)
of the Act [415 ILCS 5/22.4(d)], which requires that this Part be applicable to
"heating oil USTs," as that term is defined in Section 57.2 of the
Act [415 ILCS 5/57.2]. However, that and related terms are used in a manner that
is inconsistent with the definitions and usage in this Part. The definitions
used in this applicability statement are therefore limited to this subsection
(d).
BOARD NOTE: Owners and operators of heating oil USTs are subject to
Title XVI of the Act [415 ILCS 5/Title XVI] and therefore are required to
respond to releases in accordance with 35 Ill. Adm. Code 734 instead of Subpart
F of this Part.