35 Ill. Adm. Code 739.152
General Facility Standards
Section 739
Section 739.152Â General Facility
Standards
a)        Preparedness and Prevention. An owner or operator of a used
oil processing or re-refining facility must comply with the following
requirements:
1)        Maintenance and Operation of a Facility. All facilities must
be maintained and operated to minimize the possibility of a fire, explosion, or
any unplanned sudden or non-sudden release of used oil to air, soil, or surface
water that could threaten human health or the environment.
2)        Required Equipment. All facilities must be equipped with the
following, unless none of the hazards posed by used oil handled at the facility
could require a particular kind of equipment specified in this subsection
(a)(2):
A)Â Â Â Â Â Â Â An internal communications or alarm system capable of providing
immediate emergency instruction (voice or signal) to facility personnel;
B)Â Â Â Â Â Â Â A device, such as a telephone (immediately available at the
scene of operations) or a hand-held two-way radio, capable of summoning
emergency assistance from local police departments, fire departments, or State
or local emergency response teams;
C)Â Â Â Â Â Â Â Portable fire extinguishers, fire control equipment (including
special extinguishing equipment, such as that using foam, inert gas, or dry
chemicals), spill control equipment, and decontamination equipment; and
D)Â Â Â Â Â Â Â Water at adequate volume and pressure to supply water hose
streams, foam producing equipment, automatic sprinklers, or water spray
systems.
3)        Testing and Maintenance of Equipment. All facility communications
or alarm systems, fire protection equipment, spill control equipment, and
decontamination equipment, where required, must be tested and maintained as
necessary to assure its proper operation in time of emergency.
4)Â Â Â Â Â Â Â Â Access to Communications or Alarm System
A)Â Â Â Â Â Â Â Whenever used oil is being poured, mixed, spread, or otherwise
handled, all personnel involved in the operation must have immediate access to
an internal alarm or emergency communication device, either directly or through
visual or voice contact with another employee, unless such a device is not
required in subsection (a)(2).
B)Â Â Â Â Â Â Â If there is ever just one employee on the premises while the
facility is operating, the employee must have immediate access to a device,
such as a telephone (immediately available at the scene of operation) or a
hand-held two-way radio, capable of summoning external emergency assistance,
unless such a device is not required in subsection (a)(2).
5)        Required Aisle Space. The owner or operator must maintain
aisle space to allow the unobstructed movement of personnel, fire protection
equipment, spill control equipment, and decontamination equipment to any area
of facility operation in an emergency, unless aisle space is not needed for any
of these purposes.
6)Â Â Â Â Â Â Â Â Arrangements with Local Authorities
A)Â Â Â Â Â Â Â The owner or operator must attempt to make the following
arrangements, as appropriate for the type of used oil handled at the facility
and the potential need for the services of these organizations:
i)Â Â Â Â Â Â Â Â Â Arrangements to familiarize police, fire departments, and
emergency response teams with the layout of the facility, properties of used
oil handled at the facility and associated hazards, places where facility
personnel would normally be working, entrances to roads inside the facility, and
possible evacuation routes;
ii)Â Â Â Â Â Â Â Â If more than one police and fire department might respond to
an emergency, agreements designating primary emergency authority to a specific
police and a specific fire department, and agreements with any others to provide
support to the primary emergency authority;
iii)Â Â Â Â Â Â Â Agreements with State emergency response teams, emergency
response contractors, and equipment suppliers; and
iv)Â Â Â Â Â Â Â Arrangements to familiarize local hospitals with the
properties of used oil handled at the facility and the types of injuries or
illnesses that could result from fires, explosions, or releases at the
facility.
B)Â Â Â Â Â Â Â Where State or local authorities decline to enter into such
arrangements, the owner or operator must document the refusal in the operating
record.
b)        Contingency Plan and Emergency Procedures. An owner or operator
of a used oil processing or re-refining facility must comply with the following
requirements:
1)Â Â Â Â Â Â Â Â Purpose and Implementation of Contingency Plan
A)Â Â Â Â Â Â Â Each owner or operator must have a contingency plan for the
facility. The contingency plan must be designed to minimize hazards to human
health or the environment from fires, explosions, or any unplanned sudden or
non-sudden release of used oil to air, soil, or surface water.
B)Â Â Â Â Â Â Â The provisions of the plan must be carried out immediately
whenever there is a fire, explosion, or release of used oil that could threaten
human health or the environment.
2)Â Â Â Â Â Â Â Â Content of Contingency Plan
A)Â Â Â Â Â Â Â The contingency plan must describe the actions facility
personnel must take to comply with subsections (b)(1) and (b)(6) in response to
fires, explosions, or any unplanned sudden or non-sudden release of used oil to
air, soil, or surface water at the facility.
B)Â Â Â Â Â Â Â If the owner or operator has already prepared a Spill
Prevention Control and Countermeasures (SPCC) Plan in accordance with federal 40
CFR 112 or some other emergency or contingency plan exists for the facility
under federal, State, or local regulation (e.g., federal 40 CFR 300 or 40 CFR
280), the owner or operator need only amend that plan to incorporate used oil
management provisions that are sufficient to comply with the requirements of
this Part.
C)Â Â Â Â Â Â Â The plan must describe arrangements agreed to by local police
departments, fire departments, hospitals, contractors, and State and local
emergency response teams to coordinate emergency services, pursuant to
subsection (a)(6).
D)Â Â Â Â Â Â Â The plan must list names, addresses, and phone numbers (office
and home) of all persons qualified to act as emergency coordinator (see
subsection (b)(5)), and this list must be kept up to date. Where more than one
person is listed, one must be named as primary emergency coordinator and others
must be listed in the order in which they will assume responsibility as
alternates.
E)Â Â Â Â Â Â Â The plan must include a list of all emergency equipment at the
facility (such as fire extinguishing systems, spill control equipment,
communications and alarm systems (internal and external), and decontamination
equipment), where this equipment is required. This list must be kept up to
date. In addition, the plan must include the location and a physical
description of each item on the list, and a brief outline of its capabilities.
F)Â Â Â Â Â Â Â Â The plan must include an evacuation plan for facility
personnel where there is a possibility that evacuation could be necessary.Â
This plan must describe signals to be used to begin evacuation, evacuation
routes, and alternate evacuation routes (in cases where the primary routes could
be blocked by releases of used oil or fires).
3)        Copies of Contingency Plan. Copies of the contingency plan
and all revisions to the plan must be disposed of as follows:
A)Â Â Â Â Â Â Â Maintained at the facility; and
B)Â Â Â Â Â Â Â Submitted to all local police departments, fire departments,
hospitals, and State and local emergency response teams that may be called upon
to provide emergency services.
4)        Amendment of Contingency Plan. The contingency plan must be
reviewed, and immediately amended, if necessary, whenever one of the following
occurs:
A)Â Â Â Â Â Â Â Applicable regulations are revised;
B)Â Â Â Â Â Â Â The plan fails in an emergency;
C)       The facility changes − in its design, construction,
operation, maintenance, or other circumstances − in a way that materially
increases the potential for fires, explosions, or releases of used oil, or
changes the response necessary in an emergency;
D)Â Â Â Â Â Â Â The list of emergency coordinators changes; or
E)Â Â Â Â Â Â Â The list of emergency equipment changes.
5)        Emergency Coordinator. At all times, there must be at least
one employee either on the facility premises or on call (i.e., available to
respond to an emergency by reaching the facility within a short period of time)
with the responsibility for coordinating all emergency response measures. This
emergency coordinator must be thoroughly familiar with all aspects of the
facility's contingency plan, all operations and activities at the facility, the
location and characteristic of used oil handled, the location of all records
within the facility, and facility layout. In addition, this person must have
the authority to commit the resources needed to carry out the contingency plan.
BOARD NOTE:Â USEPA
cited the following as guidance: Â "The emergency coordinator's
responsibilities are more fully spelled out in paragraph (b)(6) of this
Section. Applicable responsibilities for the emergency coordinator vary,
depending on factors such as type and variety of used oil handled by the
facility, and type and complexity of the facility" in the note appended to
corresponding 40 CFR 279.52(b)(5).
6)Â Â Â Â Â Â Â Â Emergency Procedures
A)Â Â Â Â Â Â Â Whenever there is an imminent or actual emergency situation,
the emergency coordinator (or the designee when the emergency coordinator is on
call) must immediately do the following:
i)Â Â Â Â Â Â Â Â Â Activate internal facility alarms or communication systems,
where applicable, to notify all facility personnel; and
ii)Â Â Â Â Â Â Â Â Notify appropriate State or local agencies with designated
response roles if their help is needed.
B)Â Â Â Â Â Â Â Whenever there is a release, fire, or explosion, the emergency
coordinator must immediately identify the character, exact source, amount, and areal
extent of any released materials. He or she may do this by observation or
review of facility records or manifests and, if necessary, by chemical analyses.
C)Â Â Â Â Â Â Â Concurrently, the emergency coordinator must assess possible
hazards to human health or the environment that may result from the release,
fire, or explosion. Â This assessment must consider both direct and indirect
effects of the release, fire, or explosion (e.g., the effects of any toxic,
irritating, or asphyxiating gases that are generated, or the effects of any
hazardous surface water run-offs from water or chemical agents used to control
fire and heat-induced explosions).
D)Â Â Â Â Â Â Â If the emergency coordinator determines that the facility has
had a release, fire, or explosion that could threaten human health, or the
environment, outside the facility, he or she must report his findings as
follows:
i)Â Â Â Â Â Â Â Â Â If his assessment indicated that evacuation of local areas
may be advisable, he or she must immediately notify appropriate local
authorities. He or she must be available to help appropriate officials decide
whether local areas should be evacuated; and
ii)Â Â Â Â Â Â Â Â He must immediately notify either the government official
designated as the on-scene coordinator for the geographical area (in the
applicable regional contingency plan under federal 40 CFR 300), or the National
Response Center (using their 24-hour toll free number (800) 424-8802). The
report must include the following information: name and telephone number of
reporter; name and address of facility; time and type of incident (e.g.,
release, fire); name and quantity of materials involved, to the extent known; the
extent of injuries, if any; and the possible hazards to human health, or the
environment, outside the facility.
E)Â Â Â Â Â Â Â During an emergency, the emergency coordinator must take all
reasonable measures necessary to ensure that fires, explosions, and releases do
not occur, recur, or spread to other used oil or hazardous waste at the
facility. These measures must include, where applicable, stopping processes
and operation, collecting and containing released used oil, and removing or
isolating containers.
F)Â Â Â Â Â Â Â Â If the facility stops operation in response to a fire,
explosion, or release, the emergency coordinator must monitor for leaks,
pressure buildup, gas generation, or ruptures in valves, pipes, or other
equipment, wherever this is appropriate.
G)Â Â Â Â Â Â Â Immediately after an emergency, the emergency coordinator must
provide for recycling, storing, or disposing of recovered used oil,
contaminated soil or surface water, or any other material that results from a
release, fire, or explosion at the facility.
H)Â Â Â Â Â Â Â The emergency coordinator must ensure that the following occur,
in the affected areas of the facility:
i)Â Â Â Â Â Â Â Â Â No waste or used oil that may be incompatible with the
released material is recycled, treated, stored, or disposed of until cleanup
procedures are completed;
ii)Â Â Â Â Â Â Â Â All emergency equipment listed in the contingency plan is
cleaned and fit for its intended use before operations are resumed; and
iii)Â Â Â Â Â Â Â The owner or operator must notify the Agency and all other
appropriate State and local authorities that the facility is in compliance with
subsections (b)(6)(H)(i) and (b)(6)(H)(ii) before operations are resumed in the
affected areas of the facility.
I)Â Â Â Â Â Â Â Â The owner or operator must note in the operating record the
time, date, and details of any incident that requires implementing the
contingency plan. Within 15 days after the incident, it must submit a written
report on the incident to USEPA Region 5. The report must include the following:
i)Â Â Â Â Â Â Â Â Â The name, address, and telephone number of the owner or
operator;
ii)Â Â Â Â Â Â Â Â The name, address, and telephone number of the facility;
iii)Â Â Â Â Â Â Â The date, time, and type of incident (e.g., fire, explosion);
iv)Â Â Â Â Â Â Â The name and quantity of materials involved;
v)Â Â Â Â Â Â Â Â The extent of injuries, if any;
vi)Â Â Â Â Â Â Â An assessment of actual or potential hazards to human health
or the environment, where this is applicable; and
vii)Â Â Â Â Â Â The estimated quantity and disposition of recovered material
that resulted from the incident.