35 Ill. Adm. Code 739.154
Used Oil Management
Section 739
Section 739.154Â Used Oil
Management
A used oil processor is subject
to all applicable Spill Prevention, Control and Countermeasures (40 CFR 112) in
addition to the requirements of this Subpart F. A used oil processor or
re-refiner is also subject to the Underground Storage Tank (35 Ill. Adm. Code
731) standards for used oil stored in underground tanks whether or not the used
oil exhibits any characteristics of hazardous waste, in addition to the
requirements of this Subpart F.
a)        Management Units. A used oil processor may not store used oil
in units other than tanks, containers, or units subject to regulation under 35
Ill. Adm. Code 724 or 725.
b)        Condition of Units. The following must be true of containers
and aboveground tanks used to store or process used oil at a processing facility:
1)Â Â Â Â Â Â Â Â The containers must be in good condition (no severe rusting,
apparent structural defects or deterioration); and
2)Â Â Â Â Â Â Â Â The containers may not be leaking (no visible leaks).
c)        Secondary Containment for Containers. Containers used to
store or process used oil at processing and re-refining facilities must be
equipped with a secondary containment system.
1)Â Â Â Â Â Â Â Â The secondary containment system must consist of the following,
at a minimum:
A)Â Â Â Â Â Â Â Both of the following:
i)Â Â Â Â Â Â Â Â Â Dikes, berms, or retaining walls; and
ii)        A floor. The floor must cover the entire area within the
dike, berm, or retaining wall; or
B)Â Â Â Â Â Â Â An equivalent secondary containment system.
2)Â Â Â Â Â Â Â Â The entire containment system, including walls and floor, must
be sufficiently impervious to used oil to prevent any used oil released into
the containment system from migrating out of the system to the soil,
groundwater, or surface water.
d)Â Â Â Â Â Â Â Â Secondary Containment for Existing Aboveground Tanks.Â
Existing aboveground tanks used to store or process used oil at processing and
re-refining facilities must be equipped with a secondary containment system.
1)Â Â Â Â Â Â Â Â The secondary containment system must consist of the following,
at a minimum:
A)Â Â Â Â Â Â Â Both of the following:
i)Â Â Â Â Â Â Â Â Â Dikes, berms, or retaining walls; and
ii)        A floor. The floor must cover the entire area within the
dike, berm, or retaining wall except areas where existing portions of the tank
meet the ground; or
B)Â Â Â Â Â Â Â An equivalent secondary containment system.
2)Â Â Â Â Â Â Â Â The entire containment system, including walls and floor, must
be sufficiently impervious to used oil to prevent any used oil released into
the containment system from migrating out of the system to the soil,
groundwater, or surface water.
e)        Secondary Containment for New Aboveground Tanks. New
aboveground tanks used to store or process used oil at processing and
re-refining facilities must be equipped with a secondary containment system.
1)Â Â Â Â Â Â Â Â The secondary containment system must consist of the following,
at a minimum:
A)Â Â Â Â Â Â Â Both of the following:
i)Â Â Â Â Â Â Â Â Â Dikes, berms, or retaining walls; and
ii)        A floor. The floor must cover the entire area within the
dike, berm, or retaining wall; or
B)Â Â Â Â Â Â Â An equivalent secondary containment system.
2)Â Â Â Â Â Â Â Â The entire containment system, including walls and floor, must
be sufficiently impervious to used oil to prevent any used oil released into
the containment system from migrating out of the system to the soil,
groundwater, or surface water.
f)Â Â Â Â Â Â Â Â Labels
1)Â Â Â Â Â Â Â Â Containers and aboveground tanks used to store used oil at
processing facilities must be labeled or marked clearly with the words
"Used Oil".
2)Â Â Â Â Â Â Â Â Fill pipes used to transfer used oil into underground storage
tanks at processing facilities must be labeled or marked clearly with the words
"Used Oil".
g)        Response to Releases. Upon detection of a release of used oil
to the environment that is not subject to the federal requirements of subpart F
of 40 CFR 280 and which has occurred after October 4, 1996, a processor must
perform the following cleanup steps:
BOARD NOTE:Â
Corresponding 40 CFR 279.54(g) applies to releases that "occurred after
the effective date of the authorized used oil program for the State in which
the release is located". The Board adopted the used oil standards in
docket R93-4 at 17 Ill. Reg. 20954, effective November 22, 1993. USEPA approved
the Illinois standards at 61 Fed. Reg. 40521 (Aug. 5, 1996), effective October
4, 1996. The Board has interpreted "the effective date of the authorized
used oil program" to mean the October 4, 1996 date of federal
authorization of the Illinois program, and we substituted that date for the
federal effective date language. Had USEPA written something like "the
effective date of the used oil program in the authorized State in which the
release is located", the Board would have used the November 22, 1993
effective date of the Illinois used oil standards.
1)Â Â Â Â Â Â Â Â Stop the release;
2)Â Â Â Â Â Â Â Â Contain the released used oil;
3)Â Â Â Â Â Â Â Â Properly clean up and manage the released used oil and other
materials; and
4)Â Â Â Â Â Â Â Â If necessary, repair or replace any leaking used oil storage
containers or tanks prior to returning them to service.
h)Â Â Â Â Â Â Â Â Closure
1)        Aboveground Tanks. An owner or operator that stores or processes
used oil in aboveground tanks must comply with the following requirements:
A)Â Â Â Â Â Â Â At closure of a tank system, the owner or operator must remove
or decontaminate used oil residues in tanks, contaminated containment system
components, contaminated soils, and structures and equipment contaminated with
used oil, and manage them as hazardous waste, unless the materials are not
hazardous waste under this chapter.
B)Â Â Â Â Â Â Â If the owner or operator demonstrates that not all contaminated
soils can be practicably removed or decontaminated as required in subsection
(h)(1)(A), then the owner or operator must close the tank system and perform
post-closure care in accordance with the closure and post-closure care
requirements that apply to hazardous waste landfills (35 Ill. Adm. Code
725.410).
2)        Containers. An owner or operator that stores used oil in
containers must comply with the following requirements:
A)Â Â Â Â Â Â Â At closure, containers holding used oils or residues of used
oil must be removed from the site;
B)Â Â Â Â Â Â Â The owner or operator must remove or decontaminate used oil
residues, contaminated containment system components, contaminated soils, and
structures and equipment contaminated with used oil, and manage them as
hazardous waste, unless the materials are not hazardous waste 35 Ill. Adm. Code
721.