56 Ill. Adm. Code 6000.220
Electrical Equipment - Amusement Rides and Amusement Attractions
Section 6000
Section 6000.220 Electrical
Equipment
− Amusement Rides and Amusement Attractions
a) Effective January 1, 2010, all electrical equipment related to
amusement rides and amusement attractions must comply with NFPA 70, Article 525.
b) Lock Out. A means shall be provided for locking out the power
source to the amusement ride, amusement attraction, and equipment for
maintenance, repair or inspection. This may be a padlock latch on the main
switch.
c) High Voltage Lines. The outlets for electric power lines
carrying more than 120 volts shall be clearly marked by a contrasting color
marking pen or paint, a name label or a steel stencil imprint to show the
voltage.
d) Outdoor Apparatus and Wiring. Electrical apparatus and wiring
located outdoors shall be of such quality and so constructed or protected that
exposure to weather will not interfere with its normal operation.
e) Grounding
1) Five wire electrical systems shall be grounded at the main
power generator or main distribution panel. The neutral wire and equipment
ground shall not be bonded together at any amusement ride or amusement
attraction.
2) All other electrical systems shall have individual ground rods
connected to the amusement ride or amusement attraction frame. The neutral
wire and equipment ground shall not be bonded together at any amusement ride or
amusement attraction.
3) Sufficient electrodes to achieve 25 ohms or less resistance to
ground shall be utilized.
4) Any motor operating on 50 or more volts shall have its frame
grounded.
f) Overcurrent Protection. Conductors shall be provided with
overcurrent protection devices according to load. No such device shall be
installed in neutral or grounding conductors.
g) Receptacles and Caps. All receptacles and attachment caps
shall be of the grounding type.
h) Each amusement ride or amusement attraction not designed to be
controlled directly by the passenger shall be provided with a fused power
disconnect switch placed within arm's length of the attendant's station.
i) Safety Stop Circuits:
1) The resumption of operation after a system shutdown caused by
loss of power or activation of a safety circuit or stop shall require manual
restarting by the attendant.
2) Safety circuits shall not be bypassed during operation.
j) Emergency Lighting. If an amusement ride or amusement
attraction requires a darkened interior during operation each building or
structure shall be equipped with a battery powered emergency lighting system.
In addition to a manual switch at the attendant's station, the system shall
activate automatically when either a power failure occurs or the smoke and fire
detection alarm sounds.