77 Ill. Adm. Code 205.1750
Receptacles (Convenience Outlets)
Section 205
Section 205.1750 Receptacles
(Convenience Outlets)
a) Duplex grounding type receptacles shall be installed in all
areas or rooms in sufficient quantities for the tasks to be performed.
b) The duplex receptacles for general procedures and minor
procedures such as laser or endoscopy must be hospital grade.
c) A minimum of two duplex receptables shall be located
convenient to each examination and work table, and to each Stage I recovery
space.
d) A minimum of one duplex receptacle for each wall shall be
installed in each work area or room, other than storage or locker room.
e) Duplex receptables for cleaning equipment and general use
shall be installed in all corridors.