77 Ill. Adm. Code 205.1380
Diagnostic Facilities
Section 205
Section 205.1380Â Diagnostic
Facilities
a)Â Â Â Â Â Â Â Â Radiographic Suite: if radiographic studies are conducted, the
following shall apply:
1)Â Â Â Â Â Â Â Â Radiographic rooms shall have a minimum clear area of 120
square feet and a minimum clear dimension of 10', exclusive of vestibule,
toilet, closet, cabinet, and work counter (whether fixed or movable). A
minimum of 3'0" clearance shall be at each side and both ends of the
radiographic table;
2)Â Â Â Â Â Â Â Â A handwashing sink with a plaster trap within the room;
3)Â Â Â Â Â Â Â Â A communication system connected to the control station;
4)Â Â Â Â Â Â Â Â A film processing area with work counters, triple sink,
storage cabinets, exhaust venting for chemicals, open drains, and safety
lighting, if required by the facility operational narrative;
5)Â Â Â Â Â Â Â Â A viewing and administration area;
6)Â Â Â Â Â Â Â Â Film storage facilities, if required by the facility
operations narrative;
7)Â Â Â Â Â Â Â Â A toilet room with handwashing facilities, directly accessible
from each radiographic room without entering the general corridor area; and
8)Â Â Â Â Â Â Â Â A dressing area with convenient access to toilets and a
lockable closet unit for patient's belongings.
b)Â Â Â Â Â Â Â Â If laboratory testing is performed in the facility, the
laboratory area of the facility shall contain the following minimum facilities:
1)Â Â Â Â Â Â Â Â A laboratory work counter with sink and vacuum, and electric
services.
2)Â Â Â Â Â Â Â Â A lavatory or counter sink equipped for handwashing.
3)Â Â Â Â Â Â Â Â A storage cabinet or closet for any necessary laboratory
supplies and equipment. This storage area may be combined with other storage
areas in the center.
4)Â Â Â Â Â Â Â Â Blood collection facilities with space for a chair and work
counter.