77 Ill. Adm. Code 205.1520
Thermal and Acoustical Insulation
Section 205
Section 205.1520Â Thermal and
Acoustical Insulation
a)Â Â Â Â Â Â Â Â Insulation shall be provided for the following within the
building:
1)Â Â Â Â Â Â Â Â Boilers, smoke breeching and stacks.
2)Â Â Â Â Â Â Â Â Steam supply and condensate return piping.
3)        Hot water piping above 180°F and all hot water heaters.
4)        Hot water piping above 120°F that is exposed to contact by
patients.
5)Â Â Â Â Â Â Â Â Chilled water, refrigerant, other process piping and equipment
operating with fluid temperatures below ambient dew point.
6)Â Â Â Â Â Â Â Â Water supply and drainage piping with fluid temperatures below
ambient dew point.
7)Â Â Â Â Â Â Â Â Air ducts and casings with outside surface temperature below
ambient dew point.
8)Â Â Â Â Â Â Â Â Other piping, ducts, and equipment necessary to maintain the
efficiency of the system.
b)Â Â Â Â Â Â Â Â Insulation may be omitted from hot water and steam condensate
piping not subject to contact by patients when the insulation is unnecessary
for preventing excessive system heat loss or excessive heat gain in the
surrounding space.
c)Â Â Â Â Â Â Â Â Insulation on cold surfaces shall include an exterior vapor
barrier.
d)Â Â Â Â Â Â Â Â Insulation, including finishes and adhesives on exterior
surfaces of ducts, pipes, and equipment, shall have a flame spread rating of 25
or less and a smoke developed rating of 450 or less as determined by an
independent testing laboratory in accordance with ASTM E 84. Exception: Duct,
pipe, and equipment coverings shall not be required to meet these requirements
where they are located entirely outside the building, or do not penetrate a
wall or roof, or do not create an exposure hazard.
e)Â Â Â Â Â Â Â Â Linings in air ducts and equipment shall meet the erosion test
method described in UL Pub. No. 181. These linings, including coatings and
adhesives, and insulation on exterior surfaces of pipes and ducts in building
spaces used as air supply plenums, shall have a flame spread rating of 25 or
less and a smoke developed rating of 450 or less as determined by an
independent testing laboratory in accordance with ASTM E 84.
f)Â Â Â Â Â Â Â Â Duct linings shall not be used in systems supplying procedure
and recovery rooms/areas.