77 Ill. Adm. Code 205.1540
Air Conditioning, Heating and Ventilating Systems
Section 205
Section 205.1540Â Air
Conditioning, Heating and Ventilating Systems
a)Â Â Â Â Â Â Â Â The systems shall be designed to provide the comfort
temperatures and humidities as recommended by American Society of Heating,
Refrigerating, and Air Conditioning Engineers (ASHRAE) Standards (see Section
205.115(a)(1)(A)).
b)Â Â Â Â Â Â Â Â Air handling systems shall conform to NFPA 90A.
c)Â Â Â Â Â Â Â Â Heating, air conditioning, and ventilating systems for spaces
not exceeding 25,000 cubic feet in volume shall conform to NFPA 90B, except that
return ducts shall be constructed of materials equal to that specified for
supply ducts, Chapter 2, paragraph 1.1., Duct Materials.
d)Â Â Â Â Â Â Â Â Outdoor air intakes shall be located as far as practical, but
not less than 15 feet, from exhaust outlets of ventilation systems, combustion
equipment stacks, medical-surgical vacuum systems, and plumbing vent stacks, or
from areas that may collect vehicular exhaust and other noxious fumes.
e)Â Â Â Â Â Â Â Â All ventilation air outlets and inlets shall conform to NFPA 90A,
Chapter 2, paragraph 3.2., Location of Outlets and Inlets.
f)Â Â Â Â Â Â Â Â The ventilation systems shall be designed and balanced to
provide the ventilation and pressure relationships as shown in Table A.
g)Â Â Â Â Â Â Â Â The ventilation air supplied to the procedure rooms shall be
delivered at or near the ceiling of the area served, and all exhaust or return
air from the area shall be removed near the floor level. At least two exhaust
outlets shall be used in each procedure room.
h)Â Â Â Â Â Â Â Â All central ventilation or air conditioning systems shall be
equipped with filters having efficiencies not less than those specified in the
following table:
TABLE A
FILTER
EFFICIENCIES FOR CENTRAL VENTILATION AND AIR CONDITIONING SYSTEMS IN AMBULATORY
SURGICAL TREATMENT FACILITIES
Filter
Efficiencies (Percent)
Area Designation
Minimum
Number of Filter Beds
Filter
Bed No. 1
Filter
Bed No. 2
Procedure and Recovery Rooms
2
25
90
All Other Areas
1
25
--
i)Â Â Â Â Â Â Â Â Â All filter efficiencies shall be average atmospheric dust
spot efficiencies tested in accordance with the ASHRAE Standards 52.1, 52.2,
55, 58, 62, 63.1, 63.2, 64, and 68.
j)Â Â Â Â Â Â Â Â Â For systems serving procedure and recovery rooms, filter bed
No. 1 shall be located upstream of the air conditioning equipment, and filter
bed No. 2 shall be located downstream of the supply fan and air conditioning
equipment, including humidifiers.
k)Â Â Â Â Â Â Â Â Filter frames shall be durable and shall provide an airtight
fit with the enclosing duct work. All joints between filter segments and
enclosing duct work shall be gasketed or sealed to provide a positive seal
against air leakage.
l)Â Â Â Â Â Â Â Â Â A manometer shall be installed across each filter bed serving
procedure and recovery rooms.
m)Â Â Â Â Â Â Â Fire and smoke dampers shall be constructed, located and
installed in accordance with the requirements of NFPA 90A.
n)Â Â Â Â Â Â Â Â All systems, regardless of size, that serve more than one
smoke or fire zone shall be equipped with smoke detectors to shut down fans
automatically as specified in paragraph 4-3.1 of NFPA 90A.
o)Â Â Â Â Â Â Â Â The ventilation system for anesthesia storage rooms shall conform
to the requirements of NFPA 99, including the gravity option ventilation
system.
p)Â Â Â Â Â Â Â Â Boiler rooms shall be provided with sufficient outdoor air to
maintain combustion rates of equipment and limit temperatures in working
stations to 97ËšF Effective Temperature as defined by the ASHRAE Handbook
of Fundamentals.
q)Â Â Â Â Â Â Â Â Rooms containing heat-producing equipment, such as boiler
rooms and heater rooms, shall be insulated and ventilated to prevent any floor
surface above from exceeding a temperature of 100ËšF.
r)Â Â Â Â Â Â Â Â Â For
dates of materials incorporated by reference, see Section 205.115.