77 Ill. Adm. Code 205.1750

Receptacles (Convenience Outlets)

Last amended: 1994Year: 2026Length: 112 wordsOfficial source
Section 205 Section 205.1750  Receptacles (Convenience Outlets) a)         Duplex grounding type receptacles shall be installed in all areas or rooms in sufficient quantities for the tasks to be performed. b)         The duplex receptacles for general procedures and minor procedures such as laser or endoscopy must be hospital grade. c)         A minimum of two duplex receptables shall be located convenient to each examination and work table, and to each Stage I recovery space. d)         A minimum of one duplex receptacle for each wall shall be installed in each work area or room, other than storage or locker room. e)         Duplex receptables for cleaning equipment and general use shall be installed in all corridors.