77 Ill. Adm. Code 205.1790

Fire Alarm System

Last amended: 1994Year: 2026Length: 152 wordsOfficial source
Section 205 Section 205.1790  Fire Alarm System A manually operated electrically supervised fire alarm system shall be installed. The following is required: a)         Manual pull stations at all exit doors. b)         Audio/visual signal devices in compliance with the State of Illinois Accessibility Code (71 Ill. Adm. Code 400). c)         A presignal system is not permitted; all signals must automatically transmit to the nearest fire department or central receiving station. d)         If a sprinkler system is installed, the required water flow alarm device and electrical tamper switches must be interconnected to the fire alarm system. e)         If a smoke barrier is installed, the doors must normally be kept closed or, if held open, they must be equipped with magnetic hold-open devices that will release the door upon activation of the fire alarm system and a local smoke detector. f)         Automatic smoke detectors are required in waiting areas that are open to egress corridors.