77 Ill. Adm. Code 250.1940
Ventilation, Heating, Air Conditioning, and Air Changing Systems
Section 250
Section 250.1940Â
Ventilation, Heating, Air Conditioning, and Air Changing Systems
Ventilation, heating, air
conditioning, and air changing systems shall be provided, comply with Subpart T
or Subpart U, and shall:
a)Â Â Â Â Â Â Â Â be maintained in good repair and shall be operated in a manner
which will prevent the spread of infection and provide for patient comfort;
b)Â Â Â Â Â Â Â Â be maintained and operated in such manner that air shall not
be circulated from operating rooms, patient isolation rooms, laboratories in
which work is done in pathology, virology or bacteriology, autopsy rooms,
kitchen and dishwashing areas, toilet and bathrooms, janitors' closets, storage
rooms, shop areas and soiled linen to any other part of the facility;
c)Â Â Â Â Â Â Â Â be provided, as needed, with acceptable air filtration
equipment that is cleaned and serviced at adequate intervals; and
d)Â Â Â Â Â Â Â Â assure that the relative humidity is maintained at a minimum
of 50 percent in those areas where conductive floors are required.