77 Ill. Adm. Code 264.2750
Birth Unit Requirements
Section 264.2750Â Birth Unit Requirements
a)Â Â Â Â Â Â Â Â Size
A minimum of one centrally-located
nurses’ station shall be provided for the birth unit. The number of birth rooms
shall be provided as determined by the program narrative but shall not exceed
10 beds.
b)Â Â Â Â Â Â Â Â Client
Rooms
1)Â Â Â Â Â Â Â Â Birth
rooms. Delivery procedures shall be performed in the birth rooms. The maximum
number of beds per room is one, exclusive of bassinet. This room may also serve
as a prenatal/antepartum testing room. Rooming-in care of newborn infants is
permissible under this Part.
A)Â Â Â Â Â Â Â Location
The birth rooms shall be clustered
in groups, shall be located out of the path of unrelated traffic, and shall be
under direct supervision of the clinical staff. The birth room will serve as
labor, delivery and recovery room. The birth rooms should also be located in an
area adjacent to the respite nursery (if provided).
B)Â Â Â Â Â Â Â Space
Requirements
Birth rooms shall be adequate and
appropriate to provide for equipment, staff, supplies, and emergency procedures
required for the physical and emotional care of a maternal client, their
support person and the newborn during labor, birth, and the recovery period.
C)Â Â Â Â Â Â Â Windows
Birth rooms shall have an outside
window. The window is not required to be operable.
D)Â Â Â Â Â Â Â Hand-washing
Sinks
Each birth room shall be equipped
with a hand-washing sink with hands-free operation acceptable for scrubbing.Â
Hand-washing sinks should include accessibility standards (See Section
264.2600(c)(5)) for knee clearance and countertop height. Hand-washing sinks
shall be large and deep enough for infant bathing when not in use for hand
washing.
E)Â Â Â Â Â Â Â Bathrooms
i)Â Â Â Â Â Â Â Â Â Each
birth room shall have direct access or be adjacent to a toilet room containing
a toilet and lavatory. These bathrooms shall meet the accessibility codes per
Section 264.2600(c)(5).
ii)Â Â Â Â Â Â Â Â A
bathtub or shower shall be available for client use and may include a large tub
used for hydrotherapy for labor.
F)Â Â Â Â Â Â Â Â Floor,
Wall, and Ceiling Finishes
All finishes shall be kept clean
and shall be of the type that is appropriate for the cleaning methods and
solutions required to maintain a clean and safe environment.
G)Â Â Â Â Â Â Â Lighting
Lighting shall be provided to
accommodate the needs of the client and delivery team during labor, delivery,
and postpartum, and to permit the examination and treatment of the infant in
the infant resuscitation area.
2)Â Â Â Â Â Â Â Â If
the birth room in subsection (b)(1) is not utilized as an antepartum testing
room, the birth center shall provide a separate antepartum testing room for pregnant
persons presenting with false or suspected false labor and requiring
monitoring. These shall be provided based on the program narrative and located
as close to the nurses’ station as possible.
A)Â Â Â Â Â Â Â Antepartum
testing rooms must be a single client room and must have a minimum area of 120
square feet (11.15 square meters).
B)Â Â Â Â Â Â Â Each
antepartum testing room must be equipped with a hand-washing station.
3)Â Â Â Â Â Â Â Â Respite
Nurseries (if provided)
A respite nursery may be provided
to allow for the rest of the pregnant or postpartum person when requested. The
nursery must be located near and accessible from the nurse station and shall
meet the criteria established for newborn nurseries contained in Section
2.1.3.6.6 of the AIA Guidelines for Design and Construction of Health Care
Facilities.
4)Â Â Â Â Â Â Â Â Family
Overnight Stay Rooms (if provided)
Family overnight stay rooms must
be located in an area outside of the birth unit and clustered around a common
living/dining/nourishment preparation room. They must include the following:
A)Â Â Â Â Â Â Â An
outside window.
B)Â Â Â Â Â Â Â A
toilet room for the exclusive use of the overnight stay room, equipped with a
toilet, closet, hand-washing station, and shower.
C)Â Â Â Â Â Â Â A
storage room for clean linens and supplies within the overnight stay room area.
D)Â Â Â Â Â Â Â A
storage room for holding soiled supplies within the overnight stay room area.
E)Â Â Â Â Â Â Â A
janitor closet with slop sink and storage for cleaning supplies and cart within
the overnight stay room area.
c)Â Â Â Â Â Â Â Â Support
Areas – General
The size and location of each
support area shall depend on its use. The following support areas shall be
available in each birth center when included in the program narrative.Â
Identifiable spaces are required for each of the indicated functions.
d)Â Â Â Â Â Â Â Â Support
Areas for Birth Rooms
1)Â Â Â Â Â Â Â Â Nurse Station
A)Â Â Â Â Â Â Â The
area shall have direct visual access to the entrance to the birth unit, the
antepartum testing rooms, and the nursery (if provided).
B)Â Â Â Â Â Â Â Nurse
Stations
i)Â Â Â Â Â Â Â Â Â Nurse
stations must have adequate space for counters and storage and be located near
the hand-washing station.
ii)Â Â Â Â Â Â Â Â Nurse
stations may be combined with reception areas.
2)Â Â Â Â Â Â Â Â Documentation
Area
Charting facilities shall have a
linear surface space to ensure that staff and physicians can chart and have
simultaneous access to information and communication systems.
3)Â Â Â Â Â Â Â Â Hand-washing
Stations
A)Â Â Â Â Â Â Â Hand-washing
stations shall be easily accessible to the nurse station, medication station,
and nourishment area.
B)Â Â Â Â Â Â Â One
hand-washing station shall be permitted to serve several areas.
4)Â Â Â Â Â Â Â Â Medication
Station
Appropriate provisions shall be
made for the distribution of medications.
5)Â Â Â Â Â Â Â Â Nourishment
Area
A)Â Â Â Â Â Â Â A
nourishment area must have a sink, work counter, refrigerator, microwave,
storage cabinets, and equipment for hot and cold nourishment. This area shall
include space for trays and dishes used for nonscheduled meal service.
B)Â Â Â Â Â Â Â Hand-washing
stations shall be in or immediately accessible to the nourishment area.
6)Â Â Â Â Â Â Â Â Ice
Dispenser
Each birth center shall provide
ice for treatments and nourishment. A refrigerator with self-dispensing ice
is acceptable.
7)Â Â Â Â Â Â Â Â Clean
Workroom or Clean Supply Room
Such rooms must be separate from
and have no direct connection with soiled workrooms or soiled holding rooms and
contain storage space for clean and sterile supplies. If the clean workroom is
used for preparing client care items, it shall also contain a work counter and
a hand-washing station.
8)Â Â Â Â Â Â Â Â Soiled
Workroom or Soiled Holding Room
Such rooms shall be separate from
and have no direct connection with clean work rooms or clean supply rooms and
shall contain the following:
A)Â Â Â Â Â Â Â A
clinical sink (that is either a deep bowel free-standing wash basin sink or
equivalent flushing rim fixture) and a hand-washing sink. Both fixtures shall
have a hot and cold mixing faucet; and
B)Â Â Â Â Â Â Â A work
counter and space for separate covered containers for soiled linen and a
variety of waste types.
9)Â Â Â Â Â Â Â Â Housekeeping
Rooms
A housekeeping room must be
provided and meet the following requirements:
A)Â Â Â Â Â Â Â Contain a service sink;
B)Â Â Â Â Â Â Â Include
storage space for supplies, housekeeping equipment, and housekeeping carts; and
C)Â Â Â Â Â Â Â Be
well-ventilated and have a negative air pressure relationship to adjacent
areas.
e)Â Â Â Â Â Â Â Â Support
Areas for Staff
1)Â Â Â Â Â Â Â Â Staff
Toilet Rooms
Toilet rooms designated for staff
and visitors only must be conveniently located in the birth unit.
2)Â Â Â Â Â Â Â Â Staff
Storage Locations
Securable lockers, closets, and
cabinet compartments for the personal articles of staff shall be located in or
near the nurse station.
f)Â Â Â Â Â Â Â Â Support
Areas for Clients
1)Â Â Â Â Â Â Â Â Client and Family
Research Library and Consultation Room (if provided)
A)Â Â Â Â Â Â Â This
room must be in the public access areas but also accessible to the client
areas.
B)Â Â Â Â Â Â Â The
room must be equipped with tables, computer terminal and access ports, and
library stacks for family and client research, and study carrels. Spaces for
group seating for family and staff consultation shall also be provided. This
room may be equipped with a private consultation room for client and family
privacy.
2)Â Â Â Â Â Â Â Â Training/Conference
Room (if provided)
This room is to be used for
meetings, conferences, and childbirth educational training classes.
g)Â Â Â Â Â Â Â Â Linen
Services
Each birth center shall provide
for storing and processing of clean and soiled linen for appropriate client
care. Processing may be done within the center, in a separate building on or
off site, or in a commercial or shared laundry.
h)Â Â Â Â Â Â Â Â Waste
Management
1)Â Â Â Â Â Â Â Â Space
and facilities shall be provided for the sanitary storage and collection of
waste.
2)Â Â Â Â Â Â Â Â Waste
disposal shall be separated from the clean supplies and receiving.
i)Â Â Â Â Â Â Â Â Â Engineering
Services and Maintenance
All mechanical and electrical
equipment rooms must include sufficient space for proper maintenance, removal,
and replacement of equipment. The following shall be provided:
1)Â Â Â Â Â Â Â Â Equipment Locations.
Rooms shall be
provided for boilers, mechanical, and electrical equipment.
2)Â Â Â Â Â Â Â Â Outdoor Equipment and
Supply Storage (if necessary)
A)Â Â Â Â Â Â Â Supply
Storage
Storage for solvents and flammable
liquids shall comply with NFPA 30.
B)Â Â Â Â Â Â Â Outdoor
Equipment Storage (if required)
Yard equipment and supply storage
areas shall be provided. These must be located so that equipment may be moved
directly to the exterior without interference with other work.
j)Â Â Â Â Â Â Â Â Â Administrative
and Public Areas
The birth center must provide an
entrance at grade level, sheltered from inclement weather, and accessible to
disabled persons (in accordance with the Illinois Accessibility Code).
k)Â Â Â Â Â Â Â Â Construction
Standards
1)Â Â Â Â Â Â Â Â Building
Codes. Administrative and public areas in this Section shall be permitted to
comply with the business occupancy provisions of the Life Safety Code (NFPA
101) if they are separated from the client care portion of the birth center by
a one-hour fire rated barrier.
2)Â Â Â Â Â Â Â Â Medical
Gas. All medical and/or compressed gases shall be stored in accordance with
NFPA 99.