77 Ill. Adm. Code 300.TABLE A
A Sound Transmission Limitations in New Skilled Nursing and Intermediate Care Facilities
Section 300.TABLE Aย ย Sound
Transmission Limitations in New Skilled Nursing and Intermediate Care
Facilities
Airborne
Sound
Transmission
Class (STC)
a
Impact
Insulation
Class (11C)
b
Partitions
Floors
Floors
Residents' Room to
Residents'
Room
40
to 44
40
to 44
44
Public space to
Residents' Room
c
45
to 49
45
to 49
49
d
Service areas to
Residents'
Room
e
50
to 54
50
to 54
49
d
Notes
a
Sound transmission class (STC)
shall be determined by tests in accordance with methods set forth in ASTM Standard
E 90 and ASTM Standard E 413.
b
Impact insulation class (11C)
shall be determined in accordance with criteria set forth in HUD FT/TS-24,
"A Guide to Airborne, Impact and Structure Borne Noise-Control in
Multi-Family Dwellings."
c
Public space includes Lobbies,
Dining Rooms, Recreation Rooms, and similar spaces.
d
Impact noise limitation
applicable only when Corridor, Public Space, Service are, or Play or
Recreation Area is over patients' room.
e
Service areas include
Kitchens, Elevator Machine Rooms, Laundries, Garages, Maintenance Rooms,
Boiler and Mechanical Equipment Rooms, and similar spaces of high noise.ย
Mechanical equipment located on the same floor or above Patients; Rooms,
Offices, Nurses Stations, and similar occupied spaces shall be effectively
isolated from the floor.